Model 5128/29 Fire Slave Communicator Installation Manual

26

150805

24
Dialer
Menu

AC LOSS HOURS

Enter the number of hours before AC power loss is reported. Set to 0-15
hours for NFPA 72 Fire Alarm Systems for Central Station Service
(Chapter 4-3). Set to 15 hours for NFPA 72 Remote Supervising Station
Fire Alarm Systems. Set to 0 if you are using a fire control panel that has a
built-in delay. (Refer to the panel manual for details.)
To program a number larger than 9, use:

for 10

for 11

for 12

for 13

for 14

for 15

Note:

For all UL installations AC power loss report needs to be set from

1–3 hours.

_______
Default = 2

25
Dialer
Menu

# RINGS

Enter the number of rings before5128/29 answers a downloading call.
Options are 2-14, minimum is 2. Enter “0” to disable ring detector.

____
Default = 10

NOTES FOR STEPS 26 THROUGH 30.

Steps 26-30 apply only if the 3/1 format is selected. The 3/1 format is an old format that does not make full use of 5128/29 reporting
capabilities. The 3/1 format sends only one digit or letter for an event. It does not send the zone number with the event. Use this format
only if required by the receiver.
If you are using the 3/1 reporting format, use Steps 26-30 to select the digit (0-9) that will be sent for each event.

The letters A through E can be used if the receiver can accept them. Use

for A,

for B and so on.

Do not duplicate any digits or letters. For example, do not use “0” for both alarm code (in Step 26) and trouble code (in Step 28). Note
that the 3/1 format does not distinguish between “0” and “A”, so do not use “0” if you’re using “A” and vice versa.
See Section 6 for more information about the 3/1 format.

26
Dialer
Menu

3/1 ALARM CODE

Select the digit that will be transmitted to the central station for an alarm.
(See “NOTES” above if you need more information.)

____
Default = 1

27
Dialer
Menu

3/1 SPKLR CODE
(Feature available with
Revision H or later
boards.)

3/1 code for sprinkler supervisory conditions.
(See “NOTES” above if you need more information.)

____
Default = 2

28
Dialer
Menu

3/1 TROUBLE CODE

3/1 code for trouble conditions.
(See “NOTES” above if you need more information.)

____
Default = 8

Table 5-2: Programming Form

Step # /

From

Menu

Option

Description

Your Choice

(D) = Default

SHIFT 1

SHIFT 2

SHIFT 3

SHIFT 4

SHIFT 5

SHIFT 6

SHIFT 1

SHIFT 2