Section 1 introduction, 1 overview of basic system, 1 hardware features – SilentKnight 5808 User Manual

Page 9: 2 software features, Overview of basic system -1, 1 hardware features -1 1.1.2 software features -1

Advertising
background image

151274-L8

1-1

Section 1
Introduction

The 5808 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements
of UL 864.

1.1

Overview of Basic System

The 5808 base system is an addressable system with a built-in annunciator that can also be used to program the
system.

1.1.1

Hardware Features

•

The 5808 has one signaling line circuit (SLC) that supports 99 SK detectors and 99 SK modules or 127 SD
protocol devices.

•

6.0A of output power is available through 4 sets of terminals for notification appliance circuits or auxiliary
applications. Each circuit is power limited per UL 864 and can source up to 3.0A (total output power for all
4 circuits must not exceed 6.0A).

•

Built-in dual phone line, digital alarm communicator/transmitter (DACT).

•

Reports events to central station by point or by zone.

•

UL Listed for pre-action and deluge releasing systems.

•

Two general purpose Form C programmable relays.

•

One Form C Trouble Relay.

•

Basic system operation can be performed using a key or a user code.

•

Can be used with up to 12 Model 5860 Remote Annunciators (sold separately).

•

Can be used with Model 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on one
control panel. See Sections 4.7 and 4.8 for additional information on these models.

•

Printing of detector status, event history, and real time event log available through the Model 5824 serial/
parallel printer interface module (sold separately).

•

125 software zones, 125 output groups.

•

Add four notification/auxiliary power circuits with each 5496 Intelligent Power Module (up to 8 per
system).

1.1.2

Software Features

•

Advanced smoke detector features:
–Automatic drift compensation
–Maintenance alert region
–Point status meets calibrated smoke test requirements for NFPA 72

•

“JumpStart” feature for easy programming

•

Non-volatile event history stores 1000 events

•

A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal

•

Built-in synchronization appliance support for AMSECO, Faraday, Gentex

®

, System Sensor

®

, and

Wheelock

®

.