Figure 3. typiCAl 2-wire initiAting CirCuit ConFigurAtion, nFpA Style B:

C1074-00

wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power limited wiring only.

1. Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2. Set the address on the module per job drawings.

NOTE: Monitor module L (using terminals 6 and 7) responds at the ad-
dress set on the code switches. Monitor module H (using terminals 8 and
9) will automatically respond at the next higher address. For example, if
the code switches are set to 76, module L will respond at address 76 and
module H will respond at address 77. Use caution to avoid duplicate ad-
dressing of modules on the system.

3. Secure module to electrical box (supplied by installer), as shown in

Figure 2.

H

L

TWO INITIATING DEVICE CIRCUITS (L&H), EACH

POWER LIMITED TO 240 mA @ 11 VDC MAX.

UL LISTED CONTACT CLOSURE DEVICES MAY

BE USED. DO NOT MIX FIRE ALARM INITIATING,

SUPERVISORY, OR SECURITY DEVICES ON THE

SAME INITIATING DEVICE CIRCUIT.

INSTALL CONTACT CLOSURE DEVICES PER

MANUFACTURER’S INSTALLATION INSTRUCTIONS.

47k EOL

RESISTOR

ELR-47k

47k EOL

RESISTOR

ELR-47k

TO NEXT

DEVICE

(+)

(−)

(+)

(−)

(+)

(−)

FROM PANEL OR

PREVIOUS DEVICE

CONNECT MODULES TO LISTED

COMPATIBLE CONTROL PANELS ONLY

MONITOR L (TERMINALS 6 & 7) RESPONDS AT ADDRESS

SET ON CODE SWITCHES. MONITOR H (TERMINALS 8 &

9) RESPONDS AT NEXT HIGHER ADDRESS.

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX. SHIELDED-TWISTED

PAIR IS RECOMMENDED

MONITOR

MODULE

ALL WIRING SHOWN IS

SUPERVISED AND POWER LIMITED