SilentKnight SK-Zone-6 Addressable Six Zone Interface Module User Manual

Page 3

Advertising
background image

SK-460-008

3

I56-3441-000

In Class B operation, the remaining modules are automatically assigned to the
next five higher addresses. For example, if the base address switch is set to 28,
the next five modules will be addressed to 29, 30, 31, 32 and 33.

The module is shipped in Class B position, remove shunts for Class A. When
operating in Class A, alternate modules are paired together (+0/+1, +2/+3,
+4/+5), resulting in a total of three modules. For example, if the base ad-
dress switch is set to 28, then 30 and 32 will be automatically assigned to the
modules while 29, 31 and 33 are available to be used for other modules on the
SLC. For Class A and B operation, DO NOT set the lowest address above 94
(or 154 for panels which support 159 addresses), as the other modules will be
assigned to nonexistent addresses.

NOTE: The SK-Zone-6 must have power cycled for shunt changes to take effect.

4. A shunt is provided to disable a maximum of two unused modules in

Class B operation and Class A operation. Modules are disabled from the
highest address and work downward. If two modules are disabled, the
lowest four addresses will be functional, while the highest two will be dis-
abled. For example, in Class B operation, if the shunt for Address Disable
is placed on “two” and the base switch is set to 28, the modules will be
assigned to 28, 29, 30 and 31 while disabling the highest two positions.

NOTE: Place unused shunts on single pin to store on board for future use.

BASE ADDRESS

TO NEXT DEVICE

STATUS
INDICATORS

+

+

+0

+1

IDC

ADDRESS

+

+

+2

+3

IDC

ADDRESS

+

+

+4

+5

IDC

ADDRESS

SLC

+

+

+

+

FROM PANEL OR

PREVIOUS DEVICE

3.9K EOL

RESISTOR

(INCLUDED)

CONNECT MODULES TO

LISTED COMPATIBLE

SILENT KNIGHT CONTROL

PANELS ONLY

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.

SEE PANEL INSTRUCTION MANUAL

FOR WIRE REQUIREMENTS.

CLASS B IDC (TYPICAL)

A/B SELECT

A/B SELECT

DISABLE 1

DISABLE 2

+

+

T6

T5

DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.

INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

(–)

(+)

IN

OUT

+

+

EXTERNAL

SUPPL

Y

POWER-LIMITED

AND SUPERVISED

POWER TO THE NEXT INTERFACE

MODULE MUST BE EXTERNALLY

SWITCHED TO RESET THE DETECTORS.

AN FRM-1 RELAY CONTROL MODULE CAN BE

USED TO SWITCH POWER FROM A

STANDARD POWER SUPPLY. SEE FIGUR 10.

0

1

2

3

4

5 6

7 8 9

0

1

2

3

4

5 6

7 8 9

10

11

12

13

14

15

wIRING NOTES

Power-limited circuits must employ type FPL, FPLR, or FPLP cable as

required by Article 760 of the NEC.

All wiring must be in accordance with the NEC, NFPA 72 and all other

applicable codes and standards. All external power supplies must be
power limited with battery back-up. All external power supplies and
detectors must be UL listed for fire protection signaling applications.

PROGRAMMING
The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.

FIGURE 5: INTERFACE TwO-wIRE CONvENTIONAL DETECTORS – CLASS B, STyLE B.

C0812-01

1. To use a common power sup-

ply between multiple SK-Zone-6
modules, connect a long power
supply jumper from T5 or T6
to T5 or T6 on the adjacent SK-
Zone-6 module.

BASE ADDRESS

TO NEXT DEVICE

STATUS
INDICATORS

+

+

+0

+1

IDC

ADDRESS

+

+

+2

+3

IDC

ADDRESS

+

+

+4

+5

IDC

ADDRESS

SLC

+

+

+

+

FROM PANEL OR

PREVIOUS DEVICE

CONNECT MODULES TO LISTED COMPATIBLE

SILENT KNIGHT CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.

SEE PANEL INSTRUCTION MANUAL

FOR WIRE REQUIREMENTS.

CLASS A IDC (TYPICAL)

A/B SELECT

A/B SELECT

DISABLE 1

DISABLE 2

+

+

IDC 2

IDC 3

(–)

(+)

POWER TO THE NEXT INTERFACE

MODULE MUST BE EXTERNALLY

SWITCHED TO RESET THE DETECTORS.

AN FRM-1 RELAY CONTROL MODULE CAN BE

USED TO SWITCH POWER FROM A

STANDARD POWER SUPPLY. SEE FIGURE 10.

T6

T5

IN

OUT

+

+

EXTERNAL

SUPPL

Y

POWER-LIMITED

AND SUPERVISED

DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE. INSTALL

DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

0

1

2

3

4

5 6

7 8 9

0

1

2

3

4

5 6

7 8 9

10

11

12

13

14

15

FIGURE 6: INTERFACE TwO-wIRE CONvENTIONAL DETECTORS – CLASS A, STyLE D.

C0813-01

1. To select Class A, remove the

two shunts from the “A/B se-
lect” positions.

2. To use a common power sup-

ply between multiple SK-Zone-6
modules, connect a long power
supply jumper from T5 or T6
to T5 or T6 on the adjacent SK-
Zone-6 module.