12

Boiler (180 ºF-160 ºF) Radiant (100 ºF-120 ºF)

Chart 3: radiant/Snowmelt application Sizing

The sizing given in Chart 3 includes only a general

overview of sizing applications available. for addi-

tional or more detailed sizing parameters contact

your local Triangle Tube distributor or Triangle

Tube’s Engineering department.

The sizing given in Chart 3 does not account for any

glycol solution used in a snowmelt application.

NOTICE

NOTICE

Model

Btu/Hr

Supplied

Boiler

gPM

Pressure drop

PSI Boiler

radiant/

Snowmelt

gPM

Pressure drop

PSI radiant/

Snowmelt

TTP1-14E

25,000

2.6

0.5

2.5

0.4

TTP1-14E

30,000

3.1

0.8

3.0

0.6

TTP1-14E

35,000

3.6

1.1

3.5

0.9

TTP1-14E

40,000

4.1

1.4

4.0

1.1

TTP1-14E

45,000

4.6

1.8

4.5

1.4

TTP1-14E

50,000

5.2

2.3

5.0

1.7

TTP1-14E

55,000

5.7

2.8

5.5

2.1

TTP1-14E

60,000

6.2

3.4

6.0

2.5

TTP1-14E

65,000

6.7

4.0

6.5

2.9

TTP1-14E

70,000

7.2

4.6

7.0

3.4

TTP3-20

100,000

10.3

1.6

10.1

1.3

TTP3-20

125,000

12.9

2.6

12.6

2.1

TTP3-20

150,000

15.5

3.8

15.2

3.0

TTP3-20

175,000

18.8

5.2

17.7

4.1

TTP3-20

200,000

20.6

6.9

20.2

5.5

TTP3-20

225,000

23.2

8.8

22.7

7.0

Advertising