operation and Code restrictions

3

ProduCT aPProvalS
-

Triangle Tube’s TTP Braze Plate Heat Exchangers

are UL approved.

-

ASME is available as an option.

CodE CoMPlIanCE & rESTrICTIonS
• All piping and installations must conform with the

instructions listed in this manual and where applicable:
-

Local, state, provincial and national codes.

Where recommendations in this manual differ from

local, state or national codes, the local, state or

national codes take precedence.

The heat exchanger is a single wall exchanger and com-

plies with National Standard Plumbing Code provided:

-

Boiler / primary water (including additives) is

practically non-toxic, having a toxicity rating or

Class of 1 as listed in Clinical Toxicology of

Commercial Products, and

-

Boiler / primary water pressure is limited to max-

imum 30 psig by approved relief valve.

Single wall heat exchangers are permitted under

Uniform Plumbing Code - Paragraphs L3.2 and L3.3 if

they satisfy all of the following requirements:

1. The heat transfer medium is potable water or con-

tains only substances, which are recognized as

safe by the U.S. Food and Drug Administration.

2. The pressure of the heat transfer medium is

maintained less than the normal minimum oper-

ating pressure of the potable water system.

3. The equipment is permanently labeled to indicate

that only additives recognized as safe by the FDA

shall be used in the heat transfer medium.

other heat exchanger designs may be permitted

where approved by the administrative authority.

oPEraTIng rESTrICTIon

Max. Operating Pressure (“E” model): 150 psig
Max. Operating Pressure (Double Wall): 362 psig
Max. Operating Pressure: 450 psig
Max. Operating Temperature: 350ºF
Min. Operating Temperature: (-)320ºF
Max. Steam Pressure: 15 psi

WaTEr / fluId QualITy rESTrICTIonS

pH limit should be maintained between 6 and 8 for

copper brazed exchangers

• pH limit (minimum) of 2 for nickel braze exchangers

Chloride level of less than 80 mg/l

Sulfuric Acid or other types of corrosive acids

Highly chlorinated water such as pool water is not

acceptable and will cause premature failure.

for pool and spa application with chlorine levels up

to 3000 ppm it is recommend to use the nickel

brazed heat exchangers.

Salt water or electronic chlorinating pools and spas

is not acceptable and will cause premature failure.

for salt water or electronic chlorinating pool and

spa applications contact Triangle Tube Technical

Services for assistance in sizing a titanium plate

heat exchanger.

rEfrIgEranT rESTrICTIonS

The copper brazed heat exchangers are not compatible

with ammonia (NH3) systems. The heat exchangers with

nickel brazing are suitable for this type of application.

douBlE Wall BrazE PlaTE HEaT ExCHangEr

The TTP-5 Series DW is a true double wall heat

exchanger that provides extra protection against leak-

age while providing leak detection. This system consists

of two stainless steel plates instead of one. In case of

internal damage to the plates, the chance of fluid cross-

contamination is reduced.

for sizing applications using a double wall heat

exchanger it is recommended to contact Triangle

Tube’s Engineering department.