Blade Adjustment on Adjustable Pitch
Vaneaxial Type TCVX

Blade Angle Adjustment

The blades are set at the factory to the blade angle

that gives the performance specified on the order. This

angle should be checked prior to start-up. The patented

wheel construction uses friction and centrifugal force to

hold the blades in place. No disassembly of the wheel

is required to change the blade angles. If it is neces-

sary to change the blade angle, the following procedure

should be used:
1. Work safely. Make sure that proper safety precautions

have been followed. Electrical power must be locked

off.

2. The adjustment can be made through the inlet on

open inlet fans. On fans with ducted inlets, open the

wheel area access door.

3. Place adjustment tool around end of blade (see Figure

6, below). If necessary, apply “cheater bar” around

the 1

1

4

" diameter end for additional leverage.

The blades can be turned by hand on open inlet

fans. If additional leverage is needed, place a wrench

on the leading edge of the blade near the hub. Take

care not to mar the surface of the blade.

4.

Prior to adjusting the blade angle, check the perfor-

mance data to insure that the motor will not over-

load.

5. Turn blade to desired angle. See Figure 6. There is

an indicator mark on the hub. Align the Vernier index

line on the blade with the indicator mark on the hub.

The Vernier has the characters 3, 4, and 5 with gra-

dation lines in between. (

Note: Character 3 is 30°, 4

is 40°, 5 is 50°.) Each gradation is 2.5°. The blade

is adjustable between 25° and 50°.

6. Friction and centrifugal force will hold the blade at

the set angle. No additional adjustment is neces-

sary.

7.

Adjust all blades to the same angle.

8. Close the wheel area access door before operating

the fan.

5

4

3

Tool AS-14093

Blade Tip

Cheater Bar

Hub

Blade

Leading Edge

Detail "X"

Blade

Trailing Edge

Detail “X”

Vernier Index Line

(Blade As Shown

Is Adjusted To 35°

)

Figure 6.

Figure 5. Vertical Mounting Arrangements

Airflow

Airflow

Airflow

Airflow

4 Mounting

Holes

A

A

Discharge Down

Floor Mount

Discharge Down

Ceiling Hung

Discharge Up

Floor Mount

Discharge Up

Ceiling Hung

View A

NOTE: Fan can be supported with anchor bolts, vibration isolators,

or support rods.

25.0"

5.0"

2.5"

5