VTR83x0A5xxxB wiTh SC3500e5000 ReLAy: heATinG/CooLinG 4-pipe FAn CoiL UniT wiTh 3-Speed FAn
And 2-poSiTion VALVeS wiTh wiRed dooR SwiTCh
Configuration
Parameter Name
Configuration Settings
Fan menu
L-M-H-A
Fan cont. heat
On
BI1
Motion NO or Motion NC (remote PIR sensor only)
BI2
Door Dry
Pipe No
4
Seq. Operat
Ht-Cl
SC3500E5000
2 POSITION
COOLING VALVE
Cooling Coil
2 POSITION
HEATING VALVE
Heating Coil
Door Switch
SED-DOR-P-5000
Airflow Direction
Fan
VTR8300
Onboard
PIR Sensor
AND / OR
OR*
Wired Remote
PIR Sensor
Wireless Remote
PIR Sensor
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).