Appendix F: TeRminAL CoRReSpondenCe
The terminals of an VT8300 are identified differently and have a wider range of possible functions compared to those of any of the
VT7000 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the VT7000
series and the VT8300 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller
with a VT8300 Room Controller.
VT7000
VT8300
Terminal name
Terminal ID
Terminal name
Terminal ID
Binary Input 1
BI1
Universal Input 16
UI16
Binary Input 2
BI2
Universal Input 17
UI17
Universal Input 3
UI3
Universal Input 19
UI19
Sensor Common
Scom
Terminal 18 Common
COM
Remote Sensor
RS
Universal Input 20
UI20 - RS
Sensor Common
Scom
Terminal 21 Common
COM
Mix/Supply Sensor
MS
Universal Input 22
UI22 - SS