SCHEDULE SETTINGS
There are 7 different schedule setting screens, one for each day of the week, titled accordingly. Each day can have different scheduled
events where the room controller is set to Occupied status or back to Unoccupied status and use the appropriate setpoints, back and
forth up to 3 times per day.
- - : - -
- - : - -
****day Schedule
Occupied
Unoccupied
- - : - -
- - : - -
Occupied
Unoccupied
- - : - -
- - : - -
Occupied
Unoccupied
Screen title is identified by
day of the week (Sunday
through Saturday)
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Occupied
Default value: None
Defines a time when the room controller is automatically set to use
the Occupied setpoint.
Note: There are 3 separate Occupied parameter entries
Unoccupied
Default value: None
Defines a time when the room controller is automatically set to use
the Unoccupied setpoint.
Note: There are 3 separate Unoccupied parameter entries