VI-PIR Cover Installation

•

Remove security screw on the bottom of the current thermostat cover.

•

Open up by pulling on the bottom side of thermostat. (Fig. 3)


A)

Identify current thermostat model type:

•

Use appropriate cover accessory part number as identified on the first page by referring to the thermostat model
number

•

The male polarized PIR connector is located at bottom left corner of thermostat (Fig. 4)


B) Installation:

•

Hinge new PIR thermostat cover into position (fig. 3).

•

Insert polarized connector into PIR female connector located on thermostat base (Fig 4)

•

Snap PIR thermostat cover into place and re-install the security screw

•

Make appropriate parameter settings related to your application within the configuration menu as identified in the
thermostat installation

•

Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and
installing the thermostat and its accessories.

•

Short circuit or wrong wiring may permanently damage the thermostat or the equipment.

•

All VT7000 series thermostats are to be used only as operating controls. Whenever a control failure could
lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety
devices and/or alarm system to protect against such catastrophic failures.


Specifications

PIR cover power requirements:

5 Vdc Max current draw of 7mA

Operating conditions: 0 °C to 50 °C ( 32 °F to 122 °F )

0% to 95% R.H. non-condensing

Storage conditions: -30 °C to 50 °C ( -22 °F to 122 °F )

0% to 95% R.H. non-condensing

Sensor:

Local Passive Infra Red Sensor

Dimensions with Thermostat:

4.94” x 3.38” x 1.13”

Approximate shipping weight with Thermostat:

0.75 lb ( 0.34 kg )

Agency Approvals:

UL

UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN
XAPX (US) and XAPX7 (Canada)

FCC

Compliant to CFR 47, Part 15, Subpart B, Class A (US)

Industry Canada

ICES-003 (Canada)

CE

EMC Directive 89/336/EEC (Europe Union)

C-Tick

AS/NZS CISPR 22 Compliant (Australia / New Zealand)
Supplier Code Number N10696