Viconics C1013 User Manual

C1013 electronic thermostat

Advertising
background image

HOW TO ORDER

Thermostat

C1010-02

C1011-02 **

C1012-02

C1013-02 **

Tri-state output in cooling mode

z

z

z

z

Tri-state output reverses to heating

mode with change over sensor

z

z

Auxiliary reheat

1 stage

1 stage

** these packages include the auto change over sensor.

C1013

Electronic Thermostat

APPLICATIONS

• VAV and by-pass units control

with modulating tri-state

floating output

• Heating/Cooling change over with supply temp. sensor

Single stage of auxiliary reheat

ADVANCED DESIGN AND PI CONTROL

Advanced PI control thermostats provides precise
temperature control and eliminates wasted energy caused by
the typical On / Off cycling in conventional thermostats.
Thus the room occupant is able to reduce the thermostat
setpoint to the lowest comfortable setting. The result is
energy savings ranging from 5% to 10%.

DIMENSIONS

50

90

80

70

60

F

114 mm

32 mm

( 71 mm )

( 71 mm )

2.8"

2.8"

4.5"

1.275"

5

4

3

2

1

7

6

( 83 mm )

3.275"

SECURITY SCREW

FROM BACK

WIRING

BASE

( 71 mm )

2.8"

SCREW TERMINALS

COVER TOP

COVER INSIDE

Specifications and equipment are subject to change without prior notice.

COVERS

Factory standard scale is 10°C to 32°C for horizontal
mounting. °F & °C scales are available on special order for
horizontal or vertical mounting. The thermostat and the
terminals are an integral part of the cover. The cover hooks
onto the base for easy service and is locked in place using a
security screw.

MODULATING TRI-STATE FLOATING OUTPUT

For use with tri-state floating actuator (CW/Off/CCW) having
a 1 to 2 minutes timing per 90° of rotation. This is a true
multi positions modulating output. It gives performances
which is equivalent to more expensive 0 to 10 Vdc type
output.

HEATING / COOLING CHANGE OVER

The output is normally cooling but can be reversed to
heating mode with 2 different methods:

Auto change over to heating mode with the supplied
sensor.
1 change over sensor is used for each thermostat.
Supply temperature

< 75°F (24°C) = cooling mode

Supply temperature

> 78°F (26°C) = heating mode

Hysterisys is 3°F (2°C)
Auto change over to heating mode with a dry contact.
A closed contact on the change over input will change
operation of the tri-state output to heating mode.
Open contact = cooling mode
Closed contact = heating mode

Characteristics of change over sensor 47 K

140.0 °F

60.0 °C

11.700 Kohm

1.047 Volts

130.0 °F

54.4 °C

14.342 Kohm

1.225 Volts

120.0 °F

48.9 °C

17.682 Kohm

1.429 Volts

110.0 °F

43.3 °C

21.940 Kohm

1.659 Volts

100.0 °F

37.8 °C

27.412 Kohm

1.914 Volts

90.0 °F

32.2 °C

34.483 Kohm

2.191 Volts

80.0 °F

26.7 °C

43.704 Kohm

2.486 Volts

70.0 °F

21.1 °C

55.834 Kohm

2.791 Volts

60.0 °F

15.6 °C

71.866 Kohm

3.096 Volts

50.0 °F

10.0 °C

93.340 Kohm

3.393 Volts

40.0 °F

4.4 °C

122.298 Kohm

3.673 Volts

SINGLE STAGE OF AUXILIARY REHEAT

To be used with On/Off 2 position 24 Vac devices like:
• On/Off N.C. electric valves
• Electric duct heater relays
• Electric base board relays

See and study wiring diagrams carefully to wire reheat
devices using a separate power source.

SPECIFICATIONS

Operating

Conditions:

0 °C to 50 °C ( 32 °F to 122 °F )

0% to 95% R.H. non-condensing

Sensor:

Local 47 K NTC thermistor

Resolution:

± 0.1 °C ( ± 0.2 °F )

Control accuracy

(calibrated):

± 0.2 ° C ( ± 0.4 °F )

Ranges:

50 °F to 90 °F Standard
( 10 °C to 32 °C ) Optional

Outputs:

Isolated Triac: 30 Vac at ½ A max.

Power:

24 VAC -15%, +10% 50/60 Hz; 2 VA