C1013-02 WIRING

3

4

5

6

7

8

24 Vac

Transformer

120 Vac

Open

Close

Common

Actuator

1 to 2 minutes

timing

Field wired by installer

Change over is automatic ( non adjustable )

If supply temperature is lower than 24 C: Cooling mode

If supply temperature is higher than 25.5 C: Heating mode

3

4

5

6

7

8

24 Vac

Transformer

120 Vac

Open

Close

Common

Actuator

1 to 2 minutes

timing

Transformer ( by others )

24 Vac

120 Vac

Optional wiring schematic for applications where a

transformer is an integral part of reheat system

2

2

Change over sensor

C1013-02

Change over sensor

Single stage reheat

24 Vac relay or

24 Vac N.C. valve

R

Single stage reheat

24 Vac relay or

24 Vac N.C. valve

R

Common

24 Vac

Open

Close

Change over

Reheat

Common

24 Vac

Open

Close

Change over

Reheat

C1013-02 SEQUENCE

50 %

100%

0%

Temperature increase

Device
opened

TRUE

HEATING

SETPOINT

TRUE

COOLING

SETPOINT

DIAL SETPOINT

CENTERED

IN DEAD BAND

Device

closed

Device

on

Device

off

PROPORTIONNAL BAND

3.2 F

DEA D BAND 2.0 F

Temperature increase

TRUE

HEATING

SETPOINT

TRUE

COOLING

SETPOINT

DIAL SETPOINT

CENTERED

IN DEAD BAND

Device
opened

Device

closed

PROPORTIONNAL BAND

3.2 F

DEA D BAND 2.0 F

Device

on

Device

off

50 %

100%

0%

Damper in cooling mode

Damper in heating mode

changeover input active