CHIMNEY CONNECTIONS

Fig. 12 - Chimney Construction Through Roof

If the connector stove pipe must go through a com-

bustible wall before entering the masonry chimney, con-
sult a qualified mason or chimney dealer. The installation
must conform to local building and fire codes and latest
edition of NFPA 211 (US) or CAN/CSA-B365 (CDN).
If there is a cleanout opening in the base of the chim-
ney, close it tightly.

Chimney Minimum Height Requirements:
(1) Overall Height – 15 ft./4.6m min.
(2) Height above roof – 3 ft./91cm
(3) Height above slope – 2 ft./61cm min. within
10 ft./3.05m
(4) Minimum rise before horiz. section – 24 in./61cm

NOTICE: IF MINIMUM CHIMNEY REQUIRE-
MENTS ARE NOT MET, YOUR STOVE WILL NOT
OPERATE PROPERLY.

MANUFACTURED CHIMNEY

REFER TO CHIMNEY AND CHIMNEY CONNEC-

TOR MAKER’S INSTRUCTIONS FOR INSTALLATION
AND USE.

Use only 6”/152mm diameter listed chimney UL

103 HT (US)/ULC S629 (CDN). Chimney made to this
listing is High Temperature rated to 2100°F/1149°C. Use
chimney from only one manufacturer. Never mix brands.
Carefully follow the chimney manufacturer’s stated
requirements and clearances. Use the chimney manu-
facturer’s attic guards, roof supports, flashing, radiation
shields and fire stops when passing through a ceiling.
Use a listed wall pass-thru when passing through a
combustible wall. Do not use makeshift compromises
during installation. See Appendix on page 14.

WARNING: DO NOT USE A SINGLE-WALL CON-
NECTION PIPE AS A CHIMNEY. A HOUSE FIRE
COULD RESULT
!

When using a pre-existing chimney, have its condi-

tion and installation inspected before using. Make sure
that the chimney meets all of the UL rating requirements
listed above. Be aware that not all manufactured chim-
ney is of the UL 103 HT/ULC-S629.

NOTE: It is recommended that you contact a li-

censed heating and cooling contractor (consult your
local yellow pages) for chimney installation.

Manufactured chimney with the proper required

UL/ULC listing is available from most home centers,
hardware stores, and HVAC supply stores.

You may wish to view chimney manufacturers’

information on-line. See, www.duravent.com, www.
selkirkinc.com, or www.mtlfab.com.

Fig. 11 - Chimney Construction Through Attic Space

NOTICE: IF MINIMUM CHIMNEY REQUIRE-
MENTS ARE NOT MET, YOUR STOVE WILL NOT
OPERATE PROPERLY.

continued on next page