Fuel consumption (full load), Fuel pressure – Winco HPS9000VE/E User Manual

Page 7

Advertising
background image

7

3210-10

60706-237

You need to run a 3/4 inch line or larger from the sec-
ondary regulator to the engine-generator set. When
a two (2) regulator fuel system is used, a fuel line
size of 3/8 inch is generally adequate for distances
up to 300 feet. The line size from the table below
applies to the distance from the second regulator to
the demand regulator. A positive fuel shut-off de-
vice must be installed in the fuel line close to the
engine generator set.
This may be either a lockable
manual shut-off valve available from your local fuel
installer, or a 12 volt DC fuel solenoid valve. This
optional 12 volt DC valve is available through your
local Winco dealer.

The fuel line used to connect the supply line to the
demand regulator must be a locally approved fl exible
fuel line. Products used will vary in different regions
depending on availability and local codes. Consult
with your local fuel supplier to insure complete com-
pliance with ALL codes.

1. Remove the pipe plug from the demand regulator.

2. Connect the fl ex fuel line to the demand regulator
to the optional fuel solenoid..

DANGER: PERSONAL INJURY
Do not use galvanized pipe in the fuel line runs.
The galvanized coating will become eroded and fl ake
off, causing possible obstruction or damage to the
regulator or fuel valve. The obstruction could cause
an inoperative engine or an explosive fuel leak.

Size of pipe required for generators operating on
natural gas/LP gas.

Length of Fuel Line* Fuel Line Size

less than 25 feet

3/4 inch black pipe

25 to 100 feet

1 inch black pipe

over 100 feet

not recommended**

*allow an additional 3 feet for each standard elbow.
Do not use ‘street ells’ (restrictive)
** Consult factory for fuel runs over 100 feet.

DANGER! - FIRE - PERSONAL INJURY -
Be careful when sealing gas joints. Excessive
sealing compound can be drawn into the solenoid,
regulator or carburetor causing an engine malfunction
or dangerous fuel leak
.

FUEL CONSUMPTION (Full Load)

Gasoline

1.63Gal/HR

LP Vapor

1.9 Gal/HR

173,850 BTU

Natural Gas

180 cu ft/hr

180,000 BTU

FUEL PRESSURE

Correct fuel pressure cannot be stressed enough.
The most common cause for inoperative systems is
an inadequate or incorrect fuel pressure. Power and
performance of the engine is in direct relation to the
correctness of the fuel system. Shown below is a
block diagram of a typical L.P. or N.G. installation.

Reference numbers 1 through 3 in the block dia-
grams above are system parts supplied by customer.

Reference number 4 is the engine generator set.

Below is a table of the fuel pressure reading at each
reference in the system.

Fuel Pressure Table

Single Regulator (L.P. Vapor only)

1

3

4

UNIT OFF

TANKPSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz