Generator starting contacts, Generator exerciser circuit – Winco ULPSS15B2W/E User Manual

Page 17

Advertising
background image

7

088-00

60706-207

AUTOMATIC GENERATOR EXERCISER

This light indicates the status of the generator exer-

ciser:

- Blinks during the exercise period (including cool

down).

- stays on when the exerciser has been set.

- is off when the exerciser has not been set.

GENERATOR STARTING CONTACTS

Disconnect the generator battery. Connect the

generator starting wires #  (battery -) to terminal 4

and wire # 23 (start) to terminal 5 of the TB7 terminal

block. This is removable for convenient connections.

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to

automatically exercise the generator for 20 minutes

once every week.

In order to set and test the exercise circuit the

AUTO button on the generator control panel

must be on.

EXERCISE WITH OR WITHOUT LOAD

The transfer switch can be set up to exercise the

generator with or without a load transfer. Normally

Winco generators exercise without a load transfer.

This is because you may not wish to have a mo-

mentary interruption of power. Turn the exerciser

dipswitch on. Then set the with load or without load

dipswitch

. See table below.

Function

Factory

Setting

DIP

Switch

DIP

Actuator

Actuator

Position

clock battery

off

S2

0

on (up)

off (down)

exerciser

off

S

7

on (up)

off (down)

with load or

without load

without

load

S

8

with (up)

without

(down)

SETTING THE EXERCISER CIRCUIT

Press and hold (5 seconds) the

Set Engine Exer-

ciser button. The exercise period occurs immedi-

ately and at the same time weekly thereafter. The

status light below the button blinks during the exer-

cise period (including the cooldown). The light stays

on to indicate that the exerciser has been set. If the

light is off, the exerciser has not been set.

CANCELLING AN ACTIVE EXERCISE PERIOD

Press the

Bypass Time Delay button to stop an

exercising generator. If exercise with load is set, the

ATS retransfers the load to the utility, then stops the

generator after cooldown.

******************

***** WARNING *****

******************

WITH A TOTAL POWER FAILURE (UTILITY

POWER FAILS AND THE GENERATOR FAILS TO

START AND RUN) THE EXERCISER MUST BE

RESET AFTER THE POWER IS RESTORED.

SETTINGS

The ASCO 85 has settings that can be changed

for various applications. The dipswitch options are

explained in the ASCO 85 Operator’s Manual.

SEE THE FOLLOWING PAGE FOR SEQUENCE

OF OPERATION.

This completes your installation and unit testing.

ALWAYS leave the system in automatic mode unless

servicing the unit. For automatic operation, the auto

mode icon must be displayed on the engine control

module display.