60706-194

Page 3

0210-10

temperature, battery voltage, speed, engine load, coolant level
(from ECU), ECU specific parameters, and run-time statistics.

All metering functions are displayed on the liquid crystal display.
The front panel display begins with the SUMMARY SCREEN.
Pressing the Right arrow key will open the MAIN MENU screen.
The MAIN MENU screen consists of METERING and SETTINGS

Summary Screen

Summary screen can be set to standard or scrolling. When set to
standard, only the following are displayed:

Generator Voltage

Generator Amperage

Generator Phase

Generator Frequency

Engine Oil Pressure

Engine Coolant Temperature

Engine Battery Voltage

FUNCTIONS
DGC-2020 Digital Genset Controllers perform the following
functions:

Generator Protection and Metering

Generator protection guards against over voltage, under voltage,
under frequency, and over frequency. Over current and phase
imbalance protection is available as an option at the time of
manufacture. Each generator protection function has an adjust-
able pickup and time delay setting. Metered generator param-
eters include voltage, current, real power (watts), apparent power
(VA), and power factor (PF).

Engine Protection and Metering

Engine protection features include oil pressure and coolant
temperature monitoring, over crank protection, ECU specific
protection elements, and diagnostic reporting.
Metered engine parameters include, oil pressure, coolant

A - Liquid Crystal Display. The backlit, 64 by 128 pixel LCD
serves as the local information source for metering, alarms, pre-
alarms, and protective functions. Display operation is maintained
at -20°C. An optional LCD heater maintains display operation at -
40°C.

B - Not in Auto Indicator. This red LED lights when the DGC-
2020 is not operating in Auto mode.

C - Alarm Indicator. This red LED lights continuously during
alarm conditions and flashes during pre-alarm conditions.

D - Supplying Load Indicator. This green LED lights when the
generator current is greater than EPS threshold current.

E - Alarm Silence Push-button. Pressing this button opens the
relay output programmed as the horn output.

F - Lamp Test Push-button. Pressing this button tests the DGC-
2020 indicators by exercising all LCD pixels and lighting all LEDs.

G - Auto Push-button and Mode Indicator. Pressing the Auto
button places the DGC-2020 in Auto mode. The green Auto mode
LED lights when Auto mode is active.

H - Off Push-button and Mode Indicator. Pressing this button
places the DGC-2020 in Off mode. The red Off mode LED lights
when the DGC-2020 is in Off mode.

I - Run Push-button and Mode Indicator. Pressing this button
places the DGC-2020 in Run mode. The green Run mode LED
lights when Run mode is active.

ENGINE CONTROL
MODULE
DGC-2020