Functions, Specifications, Electrical – Winco RDP-110 User Manual

Page 10: Power input, Hardware, Communication port, Isolation, Radio, Environment, Functions -2 specifications -2

Advertising
background image

1-2

RDP-110 General Information

9318100990 Rev E

FUNCTIONS

RDP-110 remote display panel displays the following functions:

•

Switch Not in Auto Alarm

•

Low Coolant Level Alarm

•

High Coolant Temperature Alarm

•

Low Oil Pressure Alarm

•

Overcrank

Alarm

•

Overspeed

Alarm

•

Emergency Stop Alarm

•

Airbox Closed Alarm for RDP-110 X2 or fuel leak/Sender failure for RDP-110 X1.

•

Sender Failure Alarm

•

Display Panel On LED

•

Emergency System Supplying Load LED

•

High Coolant Temperature Pre-alarm

•

Low Coolant Temperature Pre-alarm

•

Low Oil Pressure Pre-alarm

•

Low Fuel Level Pre-alarm

•

Battery Overvoltage Pre-alarm

•

Weak Battery Pre-alarm

•

Battery Charger Failure Pre-alarm

SPECIFICATIONS

RDP-110 Remote Display Panels have the following specifications.

Electrical

Power Input

DC Range

8 to 32 Vdc, 2 watts maximum

AC Range

84 to 144 Vac, 5 VA maximum

Hardware

Communication Port

Interface

RS-485

Used to communicate with DGC-2020, 500, 1000,
and 2000

Isolation

1800 Vdc for one minute between chassis
ground and ac voltage input. 700 Vdc for one
minute between any of the following groups

•

Chassis

ground

•

Battery and 485 terminals

•

AC voltage inputs

Radio Frequency Interference (RFI)

Type tested using a 5 watt, hand-held
transceiver operating at random frequencies
centered around 144 and 440 megahertz with
the antenna located within 6 inches (15
centimeters) of the device in both vertical and
horizontal planes

Environment

Operating Temperature Range

-40°C to 70°C (-40°F to 158°F)

Storage Temperature Range

-40°C to 85°C (-40°F to 185°F)

Advertising