5-2

RDP-110 Testing

9318100990 Rev E

Step 9. Each LED and the horn should annunciate in the following order before repeating:

• Switch Not in Auto
• Low Coolant Level Alarm
• High Coolant Temperature Alarm
• Low Oil Pressure Alarm
• Overcrank

Alarm

• Overspeed

Alarm

• Emergency Stop Activated Alarm
• Factory selectable LED
• Sender Failure Alarm
• EPS Supplying Load
• High Coolant Temperature Pre-alarm
• Low Coolant Temperature Pre-alarm
• Low oil Pressure Pre-alarm
• Low Fuel Level Pre-alarm
• Battery Overvoltage Pre-alarm
• Weak Battery Pre-alarm
• Battery Charger Failure Pre-alarm
• Audible

Alarm

Step 10. Press and release the Alarm Silence pushbutton.

Step 11. The cycling indicators should stop when the Alarm Silence pushbutton is pressed.

Step 12. Remove the 10 Hz source and the DC power input.

Step 13. Repeat the above test procedure with AC power applied instead of the DC power.

This completes the field test procedures.