Specifications, Preparation – Winco RP25/B User Manual
Page 4

Page 2
60706-226
2030-00
SPECIFICATIONS
GENERATOR SPECIFICATIONS
RP25
KILOWATT 20
kW
KILOVOLT-AMPS (.8 PF)25 kVA
AMPERAGE
277/480 VOLT 3 PHASE 30 AMPS*
120/240
VOLT
3
PHASE
60
AMPS*
120/208
VOLT
3
PHASE
69
AMPS*
120/240
VOLT
1
PHASE
70
AMPS**
*Based on .8 power factor
**Single Phase is limited by the circuit breaker to 150
Amps on the full power terminal block - The
addtional amperage is available through receptacles.
Derate 3% per 1000 feet (305 meters) between 300 feet
(90 meters) and 7,500 feet (2,286 meters) above sea
level. Contact the factory for rating data for operation in
altitudes above 7,500 feet (2,286 meters).
For prime power application (24/7) derate all output rating
by 10%
GENERATOR RESISTANCE
RP25
Generator Make
Stamford
Generator Model
PI144F
Generator Winding
#311
Voltage Regulator
AS480
Main Stator
0.265 ohms
Main Rotor
0.708
ohms
Exciter Stator
20.3 ohms
Exciter Rotor
0.201 ohms
ENGINE SPECIFICATIONS
RP25/B
Make
Isuzu
Model
4LE1
Fuel Consumption
Full Load 1.9 gal/hr
1/2
Load
.9
gal/hr
Starting System
12 Volt DC
Fuel Diesel
Oil
API CF - CH4
SAE
10W30
8.69 Liters
Oil & Filter Replacement
250 HRS
Coolant 50/50 Mix
2.75 Gallons
Battery 12 Volt (Group 24)
650 CCA*
*Battery is not included.
TRAILER/HOUSING
RP25
Capacity
3500
lb.
Fuel Capacity 55
Gallons
Axles Single
Hitch Height Adjustable
Tires P225/75R-15
Tire Pressure 35
psi
Sound Attenuated ULTRA
QUIET
Housing Housing
Standard
PREPARATION
NOTE: This booklet covers the entire unit, EXCEPT
THE ENGINE. See the engine manufacturer’s operator
manual for specifi c maintenance and care information re-
garding the engine. Read ALL instructions in the manuals
provided before attempting to operate the generator set.
UNPACKING
When receiving the unit, be sure to inspect it carefully
for freight loss or damage. Check the nameplate to be
sure it is what you ordered (proper kW, voltage, fuel,
etc.). If you have questions, contact your local authorized
dealer. If you see evidence of loss or damage at the time
of delivery, have the driver sign and describe the loss or
damage in the “memo of loss or damage” section on the
freight bill. Then contact the carrier to get instructions on
fi ling a claim.
When loss or damage is discovered after the equipment
is delivered, but not seen at the time of delivery, it is re-
ferred to as “concealed damage.” Separate any damaged
material and contact the carrier for proper procedures to
fi le a “concealed damage” claim.
OIL REQUIREMENTS
This engine was fi lled at the factory. Before starting
check the oil level and ensure it is full. If not, refi ll to the
proper level. See engine manual for proper grade of oil.
OIL
QUANTITY
US
Qt.
Liters
RP25
9
8.7
FUEL REQUIREMENTS
See your engine operator's manual for complete type and
fuel grade information.
WARNING -NO BIODIESEL
Filling the Fuel Tank
Standard Trailer - The standard trailer is equipped with
a single 45 gallon fuel tank. Use caution when fi lling the
tank so as not to overfl ow the tank into the trailer.