Power source availability signal contacts, Programmable engine–generator exerciser – Winco ASCO 300 Accessory 11BG User Manual

Page 2

Advertising
background image

381339–252 B

ASCO POWER TECHNOLOGIES L.P.

50 Hanover Road, Florham Park, New Jersey 07932 USA

www.asco.com

page 2

2–line

display

3 buttons

connections

for power source

availability

signal contacts

J3

J1

9

wiring

J1

Figure 4. Accessory 11BG module (mounted behind operator interface and connected to the controller)

includes power source availability signal contacts and a programmable engine exerciser.

Power Source Availability Signal Contacts

The module provides one Form C contact each for the
normal and emergency power sources to signal the
acceptability of the source as sensed by the controller. The
signal contacts operate in conjunction with the Source
Available
lights on the operator interface. Field wiring
terminals are provided as shown in Figure 5 and the wiring
diagram.

Contact ratings:

2 amps @ 30 Vdc, 0.5 amp. @ 125 Vac resistive

Figure 5. Power source availability signal contacts.

Programmable Engine–Generator Exerciser

Note: Refer to your Series 300 ATS Operator’s Manual

to set DIP switches S1 & S2 in the Group 1 Controller.

A backup battery in the Series 300 ATS Group 1 Controller
(see Operator’s Manual, Sections 4 and 5) must be turned
on to maintain the settings and to allow programming with
the normal and emergency power sources turned off.
The Acc. 11BG module includes a programmable genera-
tor exerciser that provides for weekly or biweekly opera-
tion. The exerciser may have to be turned on (enabled) by
setting S1 DIP switch actuator 7 to OFF (left position), and
S2 DIP switch actuator 5 to OFF (left position).

The programmable engine–generator exerciser incorpo-
rates a 7–day or 14–day time base. Proper Group 1
Controller settings must be made to determine whether or
not the test will be done with or without load transfer
(S1 DIP switch actuator 8).

See next page for instructions on setting the exerciser.

S1 DIP Switch Settings

in Series 300 ATS Group 1 Controller

Programmable

Exerciser

Function

ACTUATORS 7 & 8

OFF ON

Enabled &

Exercise

without Load

Actuator 7 OFF

Actuator 8 OFF

7

EXER ACTV

8

LOAD

Enabled &

Exercise

with Load

Actuator 7 OFF

Actuator 8 ON

7

8

EXER ACTV

LOAD

S2 DIP Switch Settings

in Series 300 ATS Group 1 Controller

Programmable

Exerciser

Function

ACTUATOR 5

OFF ON

Enabled

Actuator 5 OFF

5

EXT EXER

Disabled

Actuator 5 ON

5

EXT EXER

Shaded DIP switches are standard factory settings.

Advertising