How to set optional programmable engine exerciser – Winco ASCO 300 Accessory 11BG User Manual

Page 3

Advertising
background image

381339–252 B

ASCO POWER TECHNOLOGIES L.P.

50 Hanover Road, Florham Park, New Jersey 07932 USA

www.asco.com

page 3

How to Set Optional Programmable Engine Exerciser

(part of Acc. 11BG module)

Hazardous voltage capable of causing shock,

burns, or death is used in this transfer switch.

Deenergize both Normal & Emergency power

sources before programming the exerciser.

Navigating the Menu

Use the UP and DOWN arrow keys to move through the
displays.

Fast/Slow Adjust

Daylight Saving

Time Adjust

Date

Time

Start TIme

Engine Exerciser

Run TIme

Changing the Parameters

Use the UP and DOWN arrow keys to move though the
displays to the parameter to be changed. Push the ENTER
key to start the editing process. The first parameter will
flash. Use the UP and DOWN arrow keys to adjust the
parameter to the desired value and press the ENTER key to
save the value. The next parameter will now flash. Repeat
the process until each parameter is properly configured.

Engine Exerciser Display

The Engine Exerciser Display shows the status of the

engine exerciser. When the unit is shipped from the factory

the programmable engine exerciser is “Disabled” and must

be set to “Enabled” by the customer. When the engine

exerciser is running, this display will count down the

remaining time until the end of the exercise period.

Start Time Display

The Start Time Display shows the engine exerciser start

time. There are four parameters that determine the start

time:

weekly (”Every”) or bi–weekly (”Alt”) operation

day of week (”Sun” through “Sat”)

start hour (0 through 23)

start minutes (0 through 59)

For example, if the user wants the exerciser to run every

other Saturday at 3 PM, the proper configuration would be:

“Alt Sat @ 15:00”

NOTE: When choosing bi–weekly operation, the exerciser

will always run on the week designated “(1)” on the date

display.

Run Time Display

The Run Time Display shows the run time for the engine

exerciser. The default setting from the factory is 30

minutes.

Time Display

The Time Display shows the present system time. The

format is “hours:minutes:seconds”.
NOTE: During total power outages, power to the accessory

is maintained by a battery in the Controller (see page 4–2 of

Operator’s Manual). Be sure that the 9–volt alkaline

battery is fresh and enabled (jumper in ON position) so that

the time and date settings are not lost.

Date Display

The Date Display shows the present system date. The

format is “day of week (week) month/day of month/year”.
NOTE: Week is either week 1 or week 2. This is used in

conjunction with the bi–weekly timer.

Daylight Savings Time Adjust Display

This display shows whether the automatic daylight saving
time adjustment is active. The factory default is “NO”. If
enabled, the unit will automatically adjust for daylight
saving time at 2 AM on the first Sunday of April and the last
Sunday of October.

Fast / Slow Adjust Display

This display shows the automatic fast/slow adjustment
value. The factory default is 0. This feature can be used to
trim a clock that runs fast or slow. For example, if your clock
runs 10 seconds slow per week, change the fast/slow adjust
value to “+10” and the unit will automatically add 10
seconds to the clock every week.
NOTE: Adjustments are made Sunday morning at 2 AM. If

you want your exerciser period to start at 2 AM on Sunday,

you cannot use this feature and the adjustment must be set

to 0.

Advertising