11. ALARMS ON LCD

ALARM Description

ICON on LCD

Beep Alarm

Low battery

1 / s

Overload: hi power consumption detected at
UPS output.

2 / s

Battery disconnected

1 / s

Batteries overcharged

1 / s

Input Cable failure

1 / s

EPO enable

1 / s

FAN failure

1 / s

Over Temperature

1 / s

Battery charger problem

1 / s

Input out of range in bypass mode

1 / s


12. TROUBLESHOOTING TABLE
Problem Description

Probable Root Cause

Suggested Action


* LCD does not show input voltage value

* AC input failure alarm active
(1 beep / 4s) however AC input source is
OK

Input power cord is not
connected

Check input power cord
connection.

Input power cord is connected
into UPS outlet.

Check input power cord
connection.

UPS cannot be powered on even AC
input is OK.
Beep alarm is active (1 beep/s) & LCD
shows:

EPO function is active.

Re-establish emergency power
off switch and set UPS in normal
mode.

USER MANUAL

Optima Rack 1-3K

___________________________________________________________________________________________________________________________________

(120217_EN) OPTIMA-RACK 1K-3K

- 20


UPS cannot be powered on even AC
input is OK.

ON push button is not been
selected properly

Push ON button during 2
seconds or longer

1 beep / s alarm is active and LCD
shows:

Input Line and Neutral are
swapped

Rotate UPS plug at wall socket
to allow correct line-neutral
connection. This suggestion is
only valid for Schuko power plug
type.

1 beep / s alarm is active and LCD
shows:

Internal or external batteries are
not properly connected

Check battery connection.

* Code 27

* Active:

* Continuous beep

Very high voltage at batteries or
charger failure

Batteries and charger must be
inspected by qualified personnel

* Code 28

* Active:

* Continuous beep

Very low voltage at batteries or
charger failure

Batteries and charger must be
inspected by qualified personnel

* Intermittent:

+

* 2 beeps per second.

UPS overloaded

Disconnect devices from UPS
outlets until solving overload

* Intermittent:

+

* 2 beeps per second.
* By-Pass activated

UPS overloaded. UPS has
changed to BYPASS mode to
avoid internal damage.

Disconnect devices from UPS
outlets until solving overload

After repetitive small overloads,
UPS has changed to BYPASS
mode.

Disconnect devices from UPS
outlets until solving overload.
Then power off UPS and re-star
again.

* Code 43

* Active:

* Continuous beep

UPS has been automatically
powered off because overload.

Disconnect devices from UPS
outlets until solving overload.
Then power ON.

* Active:

on LCD.

* Continuous beep

UPS has been automatically
powered off because short
circuit detected at output.

Check short circuit problem in
devices connected to UPS