03: Voltage range for bypass

Interface Setting

Parameter 2: Set the acceptable low voltage for bypass. Setting range is from 110V to
209V and the default value is 110V.

Parameter 3: Set the acceptable high voltage for bypass. Setting range is from 231V to
276V and the default value is 264V.


04: Frequency range for bypass

Interface Setting

Parameter 2: Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.

The default value is 46.0Hz/56.0Hz.

Parameter 3: Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.

05: ECO mode enable/disable

Interface Setting

Parameter 3: Enable or disable ECO function. You may choose following two options:
DIS: disable ECO function
ENA: enable ECO function
If ECO function is disabled, voltage range and frequency range for ECO mode still can be
set, but it is meaningless unless the ECO function is enabled.

06: Voltage range for ECO mode

Interface

Setting

Parameter 2: Low voltage point in ECO mode. The setting range is from -5% to -10% of
the nominal voltage.

Parameter 3: High voltage point in ECO mode. The setting range is from +5% to +10%
of the nominal voltage.

07: Frequency range for ECO mode

Interface Setting

Parameter 2: Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.

Parameter 3: Set high frequency point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.

The default value is 52.0Hz/62.0Hz.