16: Output voltage calibration

Interface Setting

Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output A voltage, and you
can calibrate it by pressing Up or Down according to the measurement from an external
voltage meter. The calibration result will be effective by pressing Enter. The calibration
range is limited within +/-9V. This function is normally used for parallel operation.

17: Phase auto adapt enable / disable

Interface Setting

Parameter 2: it always shows PH.A as PHASE AUTO ADAPT.
Parameter 3: it allows enable or disable this function:
DIS: Disables this function. If disable UPS only accepts 120º difference between input
lines.

ENA: Enables this function. If enable, UPS will accept input lines with same phase or a
difference of 240ºC between them.



OPTIMA 30K

Como el modelo 30K no ofrece la salida programable 2, las funciones 10 y 11 no están disponibles. Todas las demás funciones son iguales a

las de los modelos 10K y 20K.

10: Reserved

Interface Setting

Reserve for future options.

11: Reserved

Interface Setting

Reserve for future options.