Wiring Diagrams

30HR,HS

070 iJ»ru

tm

Reciprocating Liquid Chillers

60-Hertz

These diagrams apply to 30HR,HS070—120 Model A units starting

with Serial No. FI 55985 and ending with Serial No. G448588.

INDEX

UNIT

30HR,HS

070

thru

120

070,

080,

090

100

,

no,

120

FIGURE

NUMBER

DESCRIPTION

Wi ri rig For

Part-Winding Start

Suggested Field

Wiring Interlocks

’ ~T_ocdtTons o?

Control Components

Power Schernatic

Control CTrcu i t

{Simplified Schematic)

CornfroTTr i rcuit

(Simplified Schematic)

Power Schematic

'Locations of

Control Components

VOLTS

All

All

208

,

230

,

460,575

208

,

230

,

460,575

UNIT LABEL DIAGRAM

30HR

All

080-1214
080-1224

100-1584
100-1594

Re

Same As

Below

GENERAL NOTES

1.

Factory wiring is in accordance with the

National Electrical Code. Any field modifica­

tions or additions must be in compliance with
all applicable codes. Field-installed power wires
must be rated 75 C minimum.

2. Control circuit is 115-1-60, with 10-amp circuit

breaker.

3. Oil pressure safety switches are standard on

30HS units only. Jumpers between terminals] 1 |
and

and between

and

are supplied on

30HR units.

4. Manual transfer switch provides the following

starting sequences:
Three-compressor units — position 1 (terminal
A), 3-2-1; position 2 (terminal B), 1-2-3.
Four-compressor units ~ position 1 (terminal
A), 1-4-3-2; position 2 (terminal B), 3-2-1-4.

Stop unit before changing transfer switch

position.

5. All field-supplied auxiliary contacts must have a

minimum rating of 1250-va inrush and 430-va
sealed plus capacity required for field-installed

equipment between terminals 111 [ and

andpT],] 5 [and

and

12

10

6. With accessory .75-kva control transformer,

additional controls up to 3800-va inrush and

175-va sealed may be used.

7.

8

.

9.

When using a transformer, ground control

circuit by connecting green wire from trans­

former terminal X2 to ground screw (detailed
instructions with transformer package).

When using field-supplied 115-volt control

(L2) must be connected to

24

power, terminal

neutral or ground potential.

Across-the-line starting is standard on all units.

If it is necessary to modify to part-winding
start, refer to “Modification For Part-Winding

Start.”

© Carrier Corporation 1971