Carrier 38EH User Manual

Installation and start-up instructions, 38eh air-cooled condensing units, A warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING & COOLING

38EH

Air-Cooled Condensing Units

Installation and Start-Up Instructions

SAFETY CONSIDERATIONS

Installing and servicing air conditioning equipment

can be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should install or service air conditioning equipment.

Untrained personnel can perform basic maintenance,

such as cleaning and replacing filters. All other opera­
tions should be performed by trained service personnel.
When working on air conditioning equipment, observe
precautions in literature and on tags and labels attached
to unit.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for brazing operations. Have
fire

extinguisher

available.

Read

these

instructions

thoroughly. Consult local building codes and NEC
(National

Electrical

Code)

for

special

installation

requirements.

A WARNING

Before installing or servicing system, always turn

off main power to system. There may be more than
one disconnect switch. Turn off accessory heater
power if applicable. Electrical shock can cause
personal injury

Step 1 — Install on a Solid, Level Mounting

Pad

— It is recommended that unit be attached to pad

using tiedown bolts. Fasten unit to pad using holes pro­
vided in unit base. See Fig. I

When installing, allow sufficient space for airflow

clearance, wiring, refrigerant piping and service. Main­
tain a minimum of 4 ft clearance from obstructions above
and 18 in around unit (I2in. on valve side). Main­
tain a distance of 24 in. between condensing units.

Position so water or ice from roof or eaves cannot

fall directly on unit.

Step 2 — Replace Indoor AccuRater™ Piston

if Required

— Check indoor coil piston to see if it

matches the required piston listed in Table 2. If it does
not match, replace indoor coil piston with piston shipped
with this outdoor unit (located in plastic bag taped to
valves). See Fig. 2.

Step 3 — Make Piping Connections

— Outdoor

units may be connected to indoor sections using Carrier
accessory tubing package or field-supplied tubing of
refrigerant grade, correct size (see Table I) and condition.

For tubing requirements beyond 50 ft, obtain informa­

tion from Carrier distributor.

OUTDOOR

UNITS

CONNECTED

TO

CARRIER-

APPROVED INDOOR UNITS — Outdoor units con­
tain correct system refrigerant charge for operation with
indoor unit of the same size when connected by 25 ft of
field-supplied or Carrier accessory tubing. Check refrig­
erant charge for maximum efficiency (see Refrigerant
Charging)

4'0" OVERHEAD SPACE REQUIRED

FOR SERVICE AND AIRFLOW

CONTROL
BOX

LOUVERED
CASING

I DIAM
HOLE FOR^
CONTROL
WIRING

LIQUID
VALVE '
SERVICE
PORT

(HIDDEN)

SUCTION VALVE
SERVICE PORT

' AIRFLOW

I-6 AIRFLOW AND SERVICE
CLEARANCE AROUND UNIT

-I2" ON VALVE SIDE

Certified dimension drawings available upon request

Fig. 1 — Dimensions, Connections and

Mounting Pad (Refer to Table 1)

For replacement items use Carrier Specified Parts

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Bookh |4

PC101

Catalog No 533-813

PrintedinUSA

Form38EH-5SI

Pg 1

1-86

Replaces: 38EH-3SI

Tab J3a 2a

Advertising