Fig. 3 — Repair of Mechanical Connection

Compatible Fitting Repair

MECHANICAL

CONNECTION

Frontseat

unit

service valves. Relieve refrigerant pressure from tubing.

Back off locknut from Compatible Fitting onto tube.
Cut fitting between threads and 0-ring. See Fig. 3.
Remove tubing section remaining in threaded portion

of fitting. Discard locknut.

Clean, flux and insert new tube end into remaining

portion of Compatible Fitting. Wrap valve in wet rag to

prevent damaging factory-made joints. Heat and apply

low-temperature (430 F) solder.

SWEAT

CONNECTION

Frontseat

unit

service

valves. Relieve refrigerant pressure from tubing. Clean
and flux area around leak. Repair, using low-temperature
(430 F) solder

Evacuate or purge evaporator coil and tubing system.

Add refrigerant charge. See Refrigerant Charging.

Step 4 — Make Electrical Connections

— Be

sure field wiring complies with local and national fire,
safety and electrical codes, and voltage to system is
within limits shown in Table 3. Contact local power
company for correction of improper line voltage.

NOTE; Operation of unit on improper line voltage

constitutes abuse and could affect Carrier warranty. See
Table 3. Do not install unit in system where voltage may
fluctuate above or below permissible limits.

See Table 3 for recommended fuse sizes. When making

electric connections, provide clearance at unit for refrig­
erant piping connections.

INSTALL BRANCH CIRCUIT DISCONNECT PER

NEC of adequate size to handle unit starting current.

Locate disconnect within sight from and readily acces­
sible from unit, per Section 440-14 of NEC (National
Electrical Code^

ROUTE LINE POWER LEADS — Extend leads from

disconnect through power wiring hole provided (see

Fig. 1) and into unit splice area. Remove control box
cover to gain access to unit wiring.

CONNECT GROUND LEAD AND POWER WIRING
— Connect ground lead to ground connection in control
box for safety. Then connect power wiring. See Fig. 4.
Splice line power leads to yellow and black pigtails. Use
wire nuts and tape at each connection. Connect unit
wiring to copper power wiring only.

I-PHASE
CONN. TO

DISCONNECT
PER NEC

-------- GROUND LEAD -

____________________ .4=^

Q SPLICE CONNECTIONS

--------------FIELD WIRING
------------- FACTORY WIRING

-^GROUNDING LUG

-

— BLK------------------

YEL--------

I- PHASE

COND UNIT

Fig. 4 — Line Power Connections

CONNECT CONTROL POWER WIRING — Route
24-v control wires through control wiring hole and
connect to pigtails supplied with unit (Fig. 1). Splice
control leads to brown and blue pigtails on all units.
See Fig. 5.

Use furnace or fan coil transformer as 24-v (40-va

minimum) supply for system as shown in Fig. 5, or use
accessory transformer.

NOTE: Some 38EH units are equipped with a fan time
delay. This permits indoor fan to continue to operate for

Table 3 Electrical Data (60 Hz)

OUTDOOR

V/PH

OPER VOLTS*

COMPR

FAN

FLA

MCA

MAX FUSEt OR

HACR TYPE

UNIT 38EH

Max

Min

LRA

RLA

CKT BKR (Amps)

015

37 5

64

07

87

15

018

43 0

78

0.7

105

15

024

66 0

140

07

18 2

30

030

208-230/1

253

197

88 0

18 6

09

24 2

40

036

88 0

18 1

0.9

23 6

40

042

108 0

21 4

0.9

27.7

45

048

110.0

26 0

25

35.0

50

060

230/1

253

207

130 0

29 3

1 9

38.5

60

036-5

65.1

97

09

15.3

25

042-5

208-230/3

253

187

74.0

17.1

09

22.3

35

048-5

92 0

19 6

2 5

27 0

45

060-5

98 0

20 9

1.9

28.0

45

036-6

32 8

4 76

1 6

74

15

042-6
048-6

460/3

508

414

37 0
46 0

69
72

1 6
1 6

103
106

15
15

060-6

49.0

104

1 6

145

20

FLA — Full Load Amps
HACR — Heating, Air Conditioning, Refrigeration
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
RLA — Rated Load Amps

‘Permissibie iimits of the voltage range at which unit wiii operate

satisfactoriiy

fTime-delay fuse

NOTE; Controi circuit is 24 v on ali units and requires externai
power source