'l

4. Remove the cell structure which consists of a

riveted assembly of 2 end panels and 2 angles.

ROUND INSULATORS, Fig. 15, item 4, may be

lifted from the rod ends when the cell structure is
removed.

1

— Ionizer Ground Plate

2 — Cell Structure
3 — Charged and Grounded

Collector Plate Assembly

4 — Round Ceramic Insulator

5 — Contact Plate
6 — Rectangular Ceramic Insulator
7 — Bolts
8 — Sheet Metal Screws
9 — Bus Bar

Fig. 15 — Disassembled Cell, Model 31MP

RECTANGULAR INSULATORS, Fig. 15, item 6.

1. Remove the cell structure. See Disassembling

the Plate-Type Cell.

2. Remove the large bolt that holds the insulator

to the end of the plate assembly.

3.

Remove the sheet metal screw holding the

insulator and contact plate, item 5, to the end
of the bus bar, item 9.

4. Lift off insulator and contact plate.

Replacing Ionizer Wires,

Fig. 16 — The following

procedure is recommended for replacing broken
ionizer wires:

1.

Remove ionizer ground plate. See Dis­

assembling the Plate-Type Cell.

2. Remove the broken ionizer wire. Be sure no

pieces of the broken wire remain in the cell to

cause shorting.

3. Secure end of new ionizer wire in loop of

bottom ionizer wire spring.

4. Depress top ionizer wire spring with finger as in

Fig. 16.

5.

Secure top end of ionizer wire in loop of

ionizer wire spring while it is depressed.

6.

Inspect wire installation and relieve finger

pressure from ionizer wire spring.

7. Replace ionizer ground plate.

Fig. 16 — Replacing Ionizer Wire