FAULT
CODE
FAULT CODE DESCRIPTION
CHECKLIST
12 or 44
Blower Calibration Lockout or
Blower Calibration Fault
□ Check for dirty air filter
□ Check for blocked return-air or supply-air grilles throughout your home.
□ Thrn electrical power supply OFF then back ON and set the thermostat
switch to “call” for heat.
14 or 34
Pilot Proving Lockout or
Pilot Proving Fault
□ Manual shut-off valve in gas supply pipe in open position (follow
startup procedure if you open gas line).
NOTE: TUrn off the electrical power supply and remove access doors
before continuing with this checklist.
□ Control knob on gas valve in ON position (follow startup procedures if
you must reset dial to ON).
42
Inducer Outside Valid Speed Range
□ Check to make sure that all PVC pipes leading into the combustion-air
intake and vent/exhaust are free from any cracks and sags. Also check
the combustion-air intake and vent/exhaust pipes on the outside of your
home for blockage.
Any Other
Fault
13, 21, 22, 23, 24, 31, 32, 33, 41, and
43 or either RED LED on continu
ously.
□ Call dealer for service.
No Fault
Signaled
When Furnace Fails to Operate and
no Fault is Signaled
□ Check thermostat for proper temperature setting.
□ Thermostat switch on HEAT?
□ Check fuses and circuit breakers.
□ Blower door properly in place?
1. RED LED 1 on continuously means furnace is operating in emergency heat.
2. RED LED 2 on continuously means the microprocessor board has malfunctioned.
3. YEL LED 3 on continuously means furnace is operating in high heat.
4. GRN LED 4 on continuously means furnace is operating in low heat.
5. Alternate flashing of YEL and GRN LED’s indicates fault.
RED LED 2
MALFUNCTION
o
YEL
LED 3
HIGH HT '/J
n
COUNT THE
NO. OF
FLASHES
I
(
4
)
THEN
COUNT THE
NO. OF
FLASHES
I
(2) = 42 FAULT
INDUCER OUTSIDE
VALID SPEED
RANGE
1 0