Application notes

Filters

— Plenum filter racks for 008 size units can accom­

modate 2-in filters for higher filtration efficiency and/or
longer filter life. Filters other than 1-in standard must be field
supplied

Ductwork

— At installer's option, ductwork may be attached

to the curb on 50PQ units (and 50RQ units with accessory
plenum) interior installation may proceed before unit is set in
place on roof

Field power connections

— Accessory (field-installed) electric

heaters may require separate power entry to comply with local
codes Factory-installed electric heat allows single power entry

to unit for both heating and cooling

Condensate trap

— Evaporator is draw-thru configuration. A

trap (minimum 4 in deep) must be field provided prior to
start-up on cooling cycle

Static pressure limits

— When return air ductwork systems are

used, return side static pressures should be limited to 0 4

in. wg

Operating limits

— Cfm values indicated illustrate the oper­

ating range of the indoor fan Operation above or below these

limits is not recommended Exception Operation of the
50RQ008 460-3-60 unit with 15 10 electric heat ratio,
minimum cfm is 2800 at 80 F return air temperature

Remote control panel

- When use is required with emergency

heat, emergency heat switch, Carrier Part No HR59JP115
must be used Emergency heat subbase cannot be used with the
remote control panel

Low ambient cooling operation

— Units are designed to

operate at outdoor temperatures down to 35 F At tempera­
tures below 35 F, accessory Motormaster® will permit opera­
tion at outdoor temperatures as low as —20 F

Roof curb

— All curb installations must be counterflashed to

prevent water leakage.

Guide specifications

Base unit

— Furnish and install a one-piece, air-to-air electric

heat pump designed to function as a year-round air condi­

tioning system. Unit shall be completely assembled, and tested

complete with refrigerant charge and ready to operate The
total unit shall be U L listed and carry a U.L label Unit shall
be designed for either slab mount (RQ) or single-piece curb

mount (PQ) PQ unit to have outdoor air inlet with filter, plus

factory-supplied 1-in throwaway return air filters

Cooling capacity (net)

— Unit cooling cycle capacity shall be a

NET capacity with indoor fan motor heat deducted and shall
be_____ Btuh or greater total,_________ Btuh sensible at condi­

tions of______cfm air entering indoor coil, ________ F dry bulb.

___ F dry bulb entering outdoor coil

EER shall be______ .or greater when

_____ _ F wet bulb, and _

The total unit cooling

rated in accordance with ARI Standard 240 for air-to-air heat
pumps

Heating capacity

— Heating cycle capacity shall be_______ Btuh

or greater (integrated rating) when rated at_______ ,F db outdoor
ambient, with_______cfm and______ F air entering the indoor

(heating) coil The total unit C.O.P at above conditions shall

be____ or greater The ARI heating C.O.P. shall be__________ at
47 F db outdoor ambient (hi-temp),_________ at 17 F db outdoor
ambient (low temp) or greater when rated in accordance with
ARI Standard 240 for air-to-air heat pumps

Electric resistance heat

— Electric resistance heaters shall be

supplied to offset building heat loss (at winter design
conditions) when the heat pump heating cycle capacity cannot
satisfy space requirements. Fleaters shall consist of open wire

nichrome elements with controls necessary for operation

Safety controls shall include primary overtemperature and

overcurrent protection. Heaters shall be U.L. listed when
factory installed

Unit compressor(s)

shall be welded, fully hermetic with

crankcase heater(s) and suitable vibration isolators Com­
pressors shall be of the same manufacture as unit and shall be
tested and designed in unit to operate to —20 F OAT on

heating cycle without shutting off. The standard unit shall be
capable of operating to 35 F OAT. on cooling cycle Com­
pressors shall have a 5-year warranty

Coils

— Indoor and outdoor coils shall be of nonferrous

construction with aluminum plate fins mechanically bonded to
seamless copper tubes with all joints brazed.

Fans and motors

— Indoor air fan shall be forward curved,

centrifugal, belt-driven type capable of delivering___________ cfm
at_____ in. wg external static pressure Motor pulley shall be
adjustable pitch. Indoor fan shall be____________ hp with per­

manently lubricated bearings. Outdoor fan shall be of the
propeller type, with direct driven permanently lubricated
motor of_____ _hp or less. Fans shall discharge upward

Unit cabinet

shall be constructed of galvanized steel, bonder-

ized and coated with a baked enamel finish Cabinet interior

shall be insulated with 1-in. thick neoprene coated fiberglass.
Cabinet panels shall be easily removable for service to' all
operating components. A condensate drain for the indoor coil
shall be provided.

Controls

— The heat pump cooling/heating system shall be

protected with high pressurestat, low pressurestats, loss of
charge protection, indoor coil freezestats, and current and
temperature sensitive overload devices

15