HEATING A COOLING

50ET.QT

Single-Package Units

Installation, Start-Up and Service Instructions

Heat Pump and Cooling Unit Chassis Only, Sizes 212-230

CONTENTS

Page

SAFETY CONSIDERATIONS.................................... I

INTRODUCTION....................................................... 1
INSTALLATION ....................................................... 1-4
Step 1 — Check Equipment and Jobsite................I

• UNPACK UNIT
• INSPECT EQUIPMENT
• INSPECT WALL SLEEVE

Step 2 — Install Chassis in Wall Sleeve...............1-3

• INSTALL ACCESSORY OUTDOOR GRILLE
• INSTALL ACCESSORY COLD CLIMATE

PACKAGE IF REQUIRED

• SLIDE CHASSIS INTO SLEEVE

Step 3 — Install Accessory Thermostat
and Connect Thermostat Wiring........................... 3,4

• TO MOUNT THERMOSTAT IN UNIT
• TO MOUNT THERMOSTAT REMOTELY

Step 4 — Set Indoor Fan Motor Speed...................4

Step 5 — Install Accessory Electric Heater

If Required.................................................................4
START-UP................................................................4,5
SERVICE...................................................................5-I4

SAFETY CONSIDERATIONS

Installing and servicing air conditioning equipment

can be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should install or service air conditioning equipment.

Untrained personnel can perform basic maintenance,

such as cleaning and replacing filters. All other opera­
tions should be performed by trained service personnel.

When working on air conditioning equipment, observe
precautions in literature and on tags and labels attached
to unit.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for brazing operations.

Have fire extinguisher available.

A WARNING

Before installing or servicing unit, turn off main
power to system. There may be more than one

disconnect switch. Turn off accessory heater power
if applicable. Electrical shock can cause personal

injury._________________________________________

IMPORTANT: Final wiring inspection by local

authorities must be done before chassis is installed
in sleeve.

A WARNING

The Model 50ET,QT chassis is an uncased unit and,
therefore, requires special care in handling to prevent

injury to installer and damage to unit. A portable
lifting device must be used to move and position unit.

Be careful of sharp edges when handling chassis.

INTRODUCTION

Install Model 50ET air conditioner or 50QT heat pump

chassis in accessory wall sleeve. See Table 2 for part

numbers. Wall sleeves are shipped separately with accom­
panying installation instructions. All electrical power,
ductwork and condensate drain hookups are made at
time of wall sleeve installation.

IMPORTANT; Carrier standard outdoor grille or

deluxe outdoor grille must be ordered separately and
installed in wall sleeve before chassis is installed. Do
not run unit without proper outdoor grille in place.

See Table 2 for part numbers.

INSTALLATION

Step 1 — Check Equipment and Jobsite

UNPACK UNIT — Move to final location. Lift card­

board carton off chassis taking special care not to
damage unit.

INSPECT EQUIPMENT for damage prior to installa­

tion. To remove metal cover plate, remove 6 screws. File
claim with shipping company if shipment is damaged or

incomplete.

Leave chassis bolted to skid and replace metal cover

plate and carton until ready for installation into wall
sleeve.

INSPECT WALL SLEEVE installation for damage.

Condensate drain pan must be free of debris and installed
in accordance with local building regulations. Electrical
connector on left side of sleeve should be free of dirt,
grease, paint, etc. Connector must be properly wired
before chassis installation. Duct connection panel must

be level and duct connections complete. Do not rest
weight of ductwork on duct connector panel. Inspect
nameplate on sleeve to ensure wire and fuse sizing is
correct for model size and heater accessory to be installed.

NOTE: If remote thermostat location is desired, location
must be determined and field wiring must be installed
before wall completion.

Step 2 — Install Chassis in Wall Sleeve —

Remove sleeve filler panel and save screws.
INSTALL ACCESSORY OUTDOOR GRILLE — In­

stall outdoor grille using screws saved Refer to instruc­
tions shipped with outdoor grille.

INSTALL ACCESSORY COLD CLIMATE PACK­
AGE IF REQUIRED — Cold climate accessory should
be installed where the outdoor ambient temperature

consistently falls below 30 F. Refer to Table 2 for correct
accessory part number. Refer to instructions packaged

with aceessory for installation.

IMPORTANT.

Be

sure

disconnect,

per

NEC,

installed with the wall sleeve is in OFF position
before proceeding with chassis installation.