INSTALLATION

General

— Unit components are mounted to

eliminate vibration. Isolators are not required for
slab mounting. In some rooftop installations,
rubber pad-type isolators may be required due to

type of roof construction. For proper support of
unit, refer to Table 1 for weights. Pads, blocks, or
beams must be in contact with at least 4 in. of the
surface area at the ends and center of each rail
located at bottom of the unit. Regardless of the
type of mounting configuration, allow a minimum
of 12 in. under the outdoor coil for condensate
drainage. Increase to 18 in. where prolonged sub-

freezing temperatures exist. Refer to paragraph on

Roof Adapter Curb and Duct Adapter Fabrication.

Roof Mount

— Check building codes for weight

distribution requirements. Mount unit on a level

platform or frame adequate to support unit weight
and size.

Slab Mount

— Provide a level concrete slab that

extends beyond unit cabinet at least 6 in. Make
slab 8 in. thick and 4 in. above grade. Refer to

Table 1 for proper clearance under outdoor coils.
Provide a gravel apron in front of outdoor air

openings to prevent grass and foliage from ob­
structing air flow.

Rigging and Unit Placement

— Inspect unit for

transportation damage. File claim with trans­
portation agency. Do not remove shipping skid
until unit is ready to be placed. Do not drop unit.

Keep unit upright. Use spreader bars to prevent

sling or cable damage to unit (Fig. 1). Level unit

using unit frame as reference.

Locate unit as close as possible to duct open­

ings. Outdoor air inlet is not affected by wind. Do
not locate unit air inlets near exhaust vents or
other sources of contaminated air. Provide clear­
ance around and above unit for air flow, safety and
service access area as shown in Fig. 2.

Although unit is weatherproof, guard against

water from higher grade runoff and overhangs. •

Table 1 — Physical Data

UNIT 50DQ

OPERATING WEIGHT (lb)

REFRIGERANT; R-22 (lb)

COMPRESSOR

Oil PP 33-2 (pf)

OUTDOOR AIR FANS

Motor Hp ... Rpm

1-ph

3-ph

Motor Frame (NEMA)

INDOOR AIR FAN SECTION

Motor Hp ... Rpm
Motor Frame (NEMA)
Motor Pulley Range (in.)

Fan Pulley (in.)
Belt; No. ... Type ... Length (in.)
Fan Speed Range
Fan Factory Setting (Rpm)

Max Allowable Fan Speed (Rpm)
Speed change per

^2 turn of motor

movable pulley flange (Rpm)

Movable pulley factory setting

turns open

Max Allowab le full turns from

closed position

PRESSU

r

I

s

TAT SETTINGS (psig)

High cutout

cut-in

Low cutout

cut-in _

DEFROST THERMO CONTACTS -

Open
Close

GRAVirv

Fig. 1 - Rigging

EMERGENCY HEAT THERMO

CONJACTS_

_ _ ____ _____

FILTERS (factory-supplied)

No. ... Size

ANTICIPATOR SETTINGS

First Stage Heating Thermostat

Second Stage Heating Thermostat

1 relay

2 relays
3 relays

C L E A R ^

Q li IR E D U N D E R

OUTDOOR COILS

. Open
. Close

016

1853

34

06DB537

10

2

% .. 1075
%

1140

48

3 .. 1725

56

4.0 - 5.0

8.2

A48 ... 49.3

860-1060

980

1200

20

2

5

390 ± 5
290 + 15

29

i 5

64 + 5

43 F

105 F______

6 5 ± 6 F ^
80 ± 6 F

C leanable

2 .. 20 X 20 X 1

2 ... 20 X 25 X 1

4

.8

1.2

12 to 18 in.

(S)

© Carrier Corporation 1971

275

Form 50DQ-1SI