50ET,QT

Single-Package Units

triple-evacuate system to 5000 microns (29.7 in. vacuum)

before recharging. Service port connections are provided
on unit suction and discharge lines for evacuation and
charging. (See Fig. 5 for service port location.) Dial-a-
charge charging cylinder is an accurate device used to
recharge systems by weight. These cylinders are available
at refrigeration supply firms.

To check and/or adjust charge during cooling season,

use Cooling Cycle Charging Charts (Fig. 6, 8, 10, 12, 14)
and follow Charging Chart Method below. The charging
chart may also be used as an alternate method of recharg­
ing system.

To check svsiem operation during heating cycle, use

Heating Cycle Operation Check Chart (Fig. 7, 9, 11, 13,

15). These charts indicate whether a correct relationship

exists between system operating pressures and air tem­

peratures entering unit. If pressure and temperature
lines do not intersect on chart, the system refrigerant
charge may not be correct or other system abnormalities

may exist. Do not use Operating Check Charts to adjust
refrigerant charge. Weigh charge into system.

COOLING CYCLE CHARGING CHART

METHOD

1. Operate unit a minimum of 10 minutes before check­

ing charge, and after each charge adjustment.

2. Measure suction pressure by attaching a gage to unit

suction service port. (See Fig. 5 for correct service
port location.)

3 Measure outdoor (coil inlet) air dry-bulb tempera­

ture. Use service thermometer.

4. Using a sling psychrometer, measure wet-bulb tem­

perature of air entering indoor fan coil.

5. Refer to Charging Chart. Locate on curves where

outdoor air dry-bulb and indoor air wet-bulb tem­
perature lines intersect.

6. From intersect point, project vertically downward to

chart suction pressure line. Compare chart suction

pressure to unit suction pressure (step 2).

7. If unit suction pressure is lower than chart pressure,

add refrigerant to system until chart pressure is

reached If unit suction pressure is higher than chart
pressure,

remove refrigerant until chart pressure

is reached.

70

72

74

76

78

80

82

84

86

88

90

92

SUCTION PRESSURE (PSIG)

Fig. 6 — 50ET.QT212 Cooling Cycle

Charging Chart

Fig. 7 — 50QT212 Heating Operation

Check Chart

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigatlons.