Guide specifications

(cont)

Each of these devices shall be wired thru the Signal-LOC^'^

circuit to prevent compressor restart until reset at the
thermostat The standard room thermostat shall contain a

"compressor malfunction light" designed to illuminate if any

of the beforementioned safety controls trip out the compres­
sor thru the lockout circuit Two-compressor units shall have
separate and independent refrigeration and control systems
designed to allow for standby operation of either compressor

if one is locked out Two-compressor units shall have 2-stage

compressor heat and cool with built-in electric strip heat lock
out to prevent resistance heat operation above 40 F ambient

Defrost control

— An outdoor coil defrost control system

(Chronotemp®) shall be incorporated into the base unit to

prevent frost accumulation during heating cycle The defrost
cycle shall function on the basis of time and coil temperature

A 90-minute timer shall actuate a defrost mode only if coil

temperature is low enough to indicate a heavy frost condition.

Defrost shall have a positive termination time of a maximum

of 10 minutes or when the defrost thermostat is satisfied to
prevent prolonged operation on a defrost cycle Electric
resistance heaters shall be operational automatically during the
defrost cycle

Unit electrical connections

— Unit with factory-installed

electric heat shall have single point power connection to a
terminal block. Cabinet shall contain suitable openings for
routing of all utility connections The base unit shall contain a
terminal strip in the control compartment to allow for
terminal-to-terminal connection of room thermostat and field-

installed accessories

Maximum dimensions

— Width----------------- in., depth------------ in,

height-------- inches.

Accessories and options

The

following

factory-installed

options,

(FlOP)

or

field-

installed accessories (accessory) shall be provided.

Roof curb

shall be of the same manufacture as unit and shall

include an insulated panel under compressor section to prevent
condensation forming on the bottom Dimensions shall be
provided to allow for easy duct location and connection to
roof curb prior to unit placement Roof curb shall be a
minimum of 12 in high to allow for proper defrost meltage
run-off Curb design shall comply with National Roofing

Contractors Association requirements (accessory)

Economizer control

shall include R.A. and O.A dampers,

outdoor air filter and hood, and fully modulating electric
control system with O.A. thermostat and adjustable mixed air
stat. Economizer control shall be capable of introducing up to

100% outdoor air The control changeover from mechanical

cooling to economizer operation shall be fully automatic thru
an adjustable outdoor air changeover thermostat. PQ units

(accessory or FlOP) RQ units with accessory plenum
(accessory).

Alternate motor and drive assembly

to provide added cfm and

static pressure capability (FlOP)

Downturn plenum

for use on RQ units designed to easily field

attach to the base unit to direct airflow downward thru the

roof. Plenum to provide for a weatherproof opening for
ductwork assembly (accessory only on RQ units)

Electric resistance heaters

shall be available in 4 selections

(low, 75 1, 1 1 , 1 5 1 heat-to-cool ratio) and shall have open

wire nichrome elements with all necessary safety and operating

controls. Heaters shall be U.L. listed and approved for use

when factory installed. Units with factory-installed heat shall

have single power entry by terminal blocks suitable for copper
or aluminum wires (200-v, 3-phase unit with 39 Kw factory-

installed heat, copper only)

Thermostat assembly

shall provide staged heating and cooling,

manual or automatic changeover and fan control Standard

subbase shall include "compressor malfunction light" (LK-

OUT) designed to illuminate if compressor lockout is activated
(accessory)

Emergency heat control

shall consist of emergency heal

control box containing emergency heat relays and outdoor
thermostat(s), and an emergency heal thermostat subbase

(with warning light) Control shall allow for manual bypass of

compressor and outdoor thermostats if compressor becomes

inoperative, or for service Subbase light shall illuminate if

compressor lock-out is activated. Outdoor thermostats shall

provide for staging of electric resistance heal according to
outdoor temperature Thermostats shall be wired into the
electric heater contactors and shall have an adjustable set point
to provide economical resistance heat staging (accessory).

Remote control panel

to provide central unit control of

heating, cooling, indoor fan and outdoor air damper Panel
shall contain indicator lights for up lo 6 unit functions

(accessory)

Time Guard® circuit

to prevent compressor short cycling as a

result of a rapid change in thermostat setting. Also, auto­
matically prevents compressor restart at least 5 minutes after
shutdown (accessory).

Head pressure control

— A solid state outdoor fan speed

control (32LT) to maintain head pressure control down to
—20 F QAT on cooling cycle (accessory). (Inoperative during

heating cycle )

Number One
Air Conditioning

G

Division oi Carrier Corporation

Carrier Parkway • Syracuse NY 13221

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Tab 12

Form 50RQ-3P Supersedes 50RQ-2P

Primed in U S A

10-77

PC 111

Catalog No 525—044

Book 1

4

Tab

5a 5a

Advertising
This manual is related to the following products: