Carrier 50DP016 User Manual

Carrier Conditioners

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING t COOLING

50DP,DPE012,014

50DP016,020

Single-Package Cooling Units

Installation, Start-Up and Service Instructions

CONTENTS

Page

safety

considerations

........................... I

installation

. . . .

1_10

• R

oo

F

cto

'S""

................... .. • • • '

alternate

unit

support

p

*

oot

T

t

”'9

Unit................................ 1

• POSITIONING
• ROOF MOUNT

Fabricate Ductwork.......................6

Q+fE

c

Nlake Unit Duct Connections....................... 6

c

Trap Condensate Drain .................................

6

m

Make Electrical Connections................. 7

!

POWER SUPPLY
CONTROL WIRING

Make Outdoor Air Inlet

Adjustments............................................................ ...

1

outdoor

"

AIR

"

d

AMPE’

r

...........

• OPTIONAL ECONOMIZER

step 8 — Install Outdoor Air Hood......................... 10
^"FART-UP............................................................. 10-13
SERVICE..................................................................

14-16

SAFETY CONSIDERATIONS

Installation and servicing of air conditioning

ment can be hazardous due to system pressure ano

_

trical components. Only trained and

personnel should install, repair or service air condì

g

equipment.

Untrained personnel can perform basic

functions of cleaning coils and filters and rep g
filters. All other operations should ^
trained service personnel. When working on
tioning equipment, observe precautions »of“® ^ r>rpl
tags and labels attached to the unit and other sal y p
cautions that may apply.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations.

Have fire extinguishers available for all brazing

operations.

A WARNING

Before performing service or maintenance operations
on unit, turn off main power switch to unit. Electrical
shock could cause personal injury.

INSTALLATION

Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof

curb in accordance with instructions shipped with this
accessory. Accessory roof curb and information required
to field fabricate a roof curb are shown in Fig. 1 and 2.

Install insulation, cant strips, roofing and flashing as
shown. Ductwork can be installed to roof curb before unit
is set in place. Curb should be level. Unit leveling toler­
ance is ± l/16in. per linear ft in any direction. This is

necessary to permit unit drain to function properly. Refer
to Accessory Roof Curb Installation Instructions for
additional information as required.
ALTERNATE UNIT SUPPORT — When the curb

cannot be used, support unit with sleepers using unit curb

support area. If sleepers cannot be used, support long
sides of unit with a minimum of 3 equally spaced 4-in. x
4-in. pads on each side.

Step 2 — Rig and Place Unit — Inspect unit for

transportation damage. File any claim with transporta­
tion agency. Do not drop unit, keep upright. Use spreader

bars over unit to prevent sling or cable damage. Rollers
may be used to move unit across a roof Level by using

unit frame as a reference; leveling tolerance is ± 1/16 in.
per linear ft in any direction. See Fig. 3 for additional
information. Unit weight is shown in Table 1.

Four lifting holes are provided in ends of unit base rails

as shown in Fig. 3. Refer to rigging instructions on unit.

POSITIONING — Provide clearance around and above

unit for airflow, safety and service access (Fig. 4).

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

g2°k|l |4

PC111

TabTlbl6b

Catalog No 565-104

Printed in U S A

Form 50DP-26SI

ii.n,.

Carrier

Specified Parts.

Pgi

7-88

Replaces; 50DP-25SI