Table 2 — Electrical Data

UNIT

NOMINAL

V-PH-HZ

IFM

TYPE

VOLTAGE

RANGE

COMPR

(each)

OFM

IFM

COMBUSTION

FAN MOTOR

POWER SUPPLY

DISCONNECT SIZE

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP*

FLA

LRA

48LJE/LJF004

(3 Tons)

208/230-1-60

Std

187

254

179

93

1 9

2.8

57

27 1/27 1

35/35

26/26

105/105

Alt

3.8

28.1/28 1

35/35

27/27

107/107

208/230-3-60

Std

187

254

11

2

80

1 9

28

.57

18 7/18.7

25/25

18/18

92/92

Alt

38

19 7/19.7

25/25

19/19

94/94

460-3-60

Std

414

508

6

1

40

1

0

1 5

30

101

15

10

46

Alt

1.9

105

15

10

46

575-3-60

Std

518

632

45

29

1 9

2.8

57

7.5

15

7

34

Alt

38

7.9

15

8

34

48LJD/LJE/LJF

005

(4 Tons)

208/230-1-60

Std

187

254

24 8

127

1 9

38

57

36 7/36.7

45/45

35/35

141/141

Alt

57

38.6/38 6

45/45

37/37

144/144

208/230-3-60

Std

187

254

157

99

1.9

3.8

57

25 3/25.3

30/30

25/25

113/113

Alt

5.7

27 2/27.2

35/35

27/27

116/116

460-3-60

Std

414

508

78

50

1

0

1 9

.30

126

15

12

56

Alt

2.8

13.5

20

13

58

575-3-60

Std

518

632

55

40

1.9

38

57

9.2

15

9

45

Alt

5.7

9.9

15

10

47

48LJD/LJE/LJF

006

(5 Tons)

230-1-60

Std

187

254

27.8

135

1 9

85

.57

45 2

60

44

164

208/230-3-60

187

254

19.2

105

1 9

8.5

.57

34.4/34.4

40/40

34/34

134/134

460-3-60

414

508

96

55

1

0

4.5

30

17.5

20

17

81

575-3-60

518

632

83

45

1 9

85

.57

14.5

20

14

57

48LJD/LJE/LJF

007

(6 Tons)

208/230-3-60

Std

187

254

21 9

142

1 9

5.8

57

35.1/35.1

40/40

34/34

188/188

460-3-60

414

508

104

72

1

0

2.6

30

16.6

20

16

95

575-3-60

518

632

96

58 5

1 9

11

0

57

172

20

17

81

IMPORTANT: Optional, alternate evaporator-fan motor and drive are not
available for 48LJ006,007 units. Contact your local Carrier representative
for more information about field-installed motors

LEGEND

Compressor
Full Load Amps
Heating, Air Conditioning and Refrigeration

Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
Outdoor (Condenser) Fan Motor
Rated Load Amps

COMPR
FLA
HACR
IFM

LRA
MCA
MOCP
OFM
RLA

*Fuse or HACR circuit breaker

NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multi­

motor and combination load equipment (refer to NEC Articles 430 and 440),
the overcurrent protective device for the unit shali be fuse or HACR breaker
Canadian Standards Association (CSA) units may be fuse or circuit breaker

2 Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalanoe in supply voltage is greater
than 2% Use the following formula to determine the percent voltage im­
balance.

% Voltage Imbalance

max voltage deviation from average voltage

Example: Supply voltage is 460-3-60.

AB = 452V

ABC

BC = 464v
AC = 455V

Average Voltage

452 4- 464 4- 455

_ 1371

3

= 457

NOTE: The 575-v units are CSA only

Determine maximum deviation from average voltage
(AB) 457 - 452 = 5

V

(BC) 464 - 457 = 7

V

(AC) 457 - 455 = 2

V

Maximum deviation is 7 v.
Determine % voltage imbalance

7

% Voltage Imbalance = 100 x -----------

457

= 1 53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%

IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately

100

X

average voltage

Advertising