OUTDOOR AIRFLOW (cfm x 100)

Example:

Given —

Return-Air Negative Static Pressure .........................0 2 in wg

Outdoor Air

...................................................... 900 cfm

Determine —

Setting = 5

Fig. 22 — Economizer Damper Minimum Position Setting

Fig. 23 - Minimum Position Damper Setting

Step 9 — Adjust Evaporator-Fan Speed

— Ad­

just evaporator-fan speed to meet jobsite conditions.

Table 3 shows fan rpm at motor pulley settings. Refer to
Tables 4-15 to determine fan speed settings.

DIRECT DRIVE MOTORS — The evaporator-fan motor
factory speed setting is shown on label diagram affixed to
base unit. If other than factory setting is desired, refer to
label diagram for motor reconnection.

BELT DRIVE MOTORS — Ean motor pulleys are factory

set for speed shown in Table 1.

NOTE: Before adjusting fan speed, make sure the new fan

speed will provide an air temperature rise range as shown
in Table 1.
To change fan speed:

1. Shut off unit power supply.

2. Loosen belt by loosening fan motor mounting nuts. See

Fig. 26.

3. Loosen movable pulley flange setscrew (see Fig. 27).

4. Screw movable flange toward fixed flange to increase

speed and away from fixed flange to decrease speed. In­
creasing fan speed increases load on motor. Do not ex­
ceed maximum speed specified in Table 1.

5. Set movable flange at nearest key way of pulley hub and

tighten setscrew. (See Table 1 for speed change for each
full turn of pulley flange.)