TROUBLESHOOTING

Table 18 — LED Error Code Service Analysis

PROBLEM

CAUSE

REMEDY

Hardware failure.
(LED OFF)

Loss of power to control module (IGC).

Check 5 amp fuse on IGC, power to unit, 24 v circuit
breaker, and transformer. Units without a 24 v circuit
breaker have an internai overload in the 24 v trans­
former if the overload trips, aliow 10 minutes for auto­

matic reset.

Limit switch fauit.

(LED 2 fiashes)

High temperature iimit switch is open.

Check the operation of the indoor (evaporator) fan mo­
tor. Ensure that the suppiy-air temperature rise is in ac­
cordance with the range on the unit namepiate.

Fiame sense fauit.
(LED 3 fiashes)

The IGC sensed flame that should not be present

Reset unit. If problem persists, repiace controi board

4 consecutive iimit
switch trips.
(LED 4 fiashes)

Inadequate airflow to unit.

Check operation of indoor (evaporator) fan motor and
that suppiy-air temperature rise agrees with range on
unit nameplate information.

Ignition lockout.
(LED 5 flashes)

Unit unsuccessfully attempted ignition for 15 minutes.

Check ignitor and flame sensor electrode spacing, gaps,
etc. Ensure that flame sense and ignition wires are prop­
erly terminated. Verify that unit is obtaining proper
amount of gas.

Induced-draft motor

fault.

(LED 6 flashes)

iGC does not sense that induced-draft motor is

operating.

Check for proper voltage. If motor Is operating, check
the speed sensor plug/IGC Terminal J2 connection.

Proper connection: PIN 1 — White, PIN 2 — Red, PIN 3

— Black.

Rollout switch fault.

(LED 7 flashes)

Rollout switch has opened.

Rollout switch will automatically reset, but IGC will con­

tinue to lockout unit. Check gas valve operation. Ensure
that induced-draft blower wheel is properly secured to

motor shaft. Reset unit at unit disconnect.

Internal control fault.
(LED 8 flashes)

Microprocessor has sensed an error in the software or
hardware.

If error code Is not cleared by resetting unit power, re­

place the IGC.

IMPORTANT; Refer to Table 19 — Heating Service Analysis for

additional troubleshooting analysis.

LEGEND

IGC — Integrated Gas Unit Controller