TROUBLESHOOTING CHART

Table 10—Cooling Sen/ice Analysis Chart

SYMPTOM

PROBABLE CAUSE

REMEDY

Compressor and condenser fan
will not start

Power failure

Call power company.

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker.

Defective thermostat, contactor,
transformer, or control relay

Replace component

Insufficient line voltage

Determine cause and correct.

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not start
but condenser fan runs

Faulty wiring or loose connections

in compressor circuit

Check wiring and repair or replace.

Compressor motor burned out, seized,

or internal overload open

Determine cause Replace compressor.

Defective run/start capacitor,

overload, start relay

Determine cause and replace.

One leg of 3-phase power dead

Determine cause. Replace fuse or reset circuit breaker.

Compressor cycle (other than
normally satisfying thermostat)

Refrigerant overcharge or undercharge

Blow refrigerant, evacuate system, and recharge to nameplate.

Defective compressor

Determine cause, replace.

Insufficient line voltage

Determine cause and correct.

Blocked condenser

Determine cause and correct.

Defective run/start capacitor, overload,

or start relay

Determine cause and replace.

Defective thermostat

Replace thermostat.

Faulty condenser fan motor or capacitor

Replace.

Restriction in refrigerant system

Locate restriction and remove.

Compressor operates
continuously

Dirty air filter

Replace filter.

Unit undersized for load

Decrease load or increase unit size.

Thermostat set too low

Reset thermostat.

Low refrigerant charge

Locate leak, repair, and recharge.

Leaking valves in compressor

Replace compressor.

Air in system

Blow refrigerant, evacuate system, and recharge.

Condenser coil dirty or restricted

Clean coil or remove restriction.

Excessive head pressure

Dirty air filter

Replace filter.

Dirty condenser coil

Clean coil.

Refrigerant overcharged

Purge excess refrigerant.

Air in system

Blow refrigerant, evacuate system, and recharge.

Condenser air restricted or air

short-cycling

Determine cause and correct.

Head pressure too low

Low refrigerant charge

Check for leaks, repair, and recharge.

Compressor valves leaking

Replace compressor.

Restriction in liquid tube

Remove restriction.

Excessive suction pressure

High heat load

Check for source and eliminate.

Compressor valves leaking

Replace compressor.

Refrigerant overcharged

Purge excess refrigerant.

Suction pressure too low

Dirty air filter

Replace filter.

Low refrigerant charge

Check for leaks, repair, and recharge.

Metering device or low side restricted

Remove source of restriction.

Insufficient evaporator airflow

Increase air quantity. Check filter—replace if necessary.

Temperature too low in conditioned area

Reset thermostat.

Outdoor ambient below 55 F

Install accessory low-ambient kit.

Field-installed filter drier restricted

Replace.

?1