Single-stage heat s cool- autochangeover, Frrw, N-rvri – Carrier 48KHA User Manual

Page 8: Fig. 8—high- and low-voitage connections, Table 3—electrical data (60 hz)

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 3—Electrical Data (60 Hz)

MODEL

48-

SERIES

VOLTS-

PHASE

OPERATING

VOLTAGE*

COMPR

FLA

MCAt

MAX

AMPS

MAX FUSE

SIZE

(Amps)t

MIN WIRE

SIZE (AWG)t

(75C Copper)

MAX

WIRE

LENGTHt

Min

Max

RLA

LRA

IFM

OFM

KLA118

310BE

208/230-1

197

253

8.7

49.0

1.2

1.0

13.1

10.9

20

14

76

KLA124

310BE

208/230-1

197

253

11.7

63.0

1.7

1.0

17.4

14.4

25

12

89

KHA024

310BF

208/230-1

197

253

11.7

63.0

3.0

1.0

18.7

15.7

25

12

82

KLA130

310BE

208/230-1

197

253

13.7

76.0

3.1

1.0

21.2

17.8

30

10

115

KHA030

310BF

208/230-1

197

253

13.7

76.0

2.9

1.0

21.0

17.6

30

10

116

KLA136

310BE

208/230-1

197

253

17.6

88.0

4.6

1.0

27.6

23.2

40

10

88

KLA136

510CE

208/230-3

187

253

11.5

65.1

4.7

1.0

20.1

17.2

25

10

137

KLA136

610CE

460-3

414

506

5.1

32.8

1.9

0.6

8.9

7.6

15

14

272

KHA136
KHA036

310BE
310BF

208/230-1

197

253

17.6

88.0

3.8

0.8

26.6

22 2

40

10

92

KHA136

510CE,CF

208/230-3

187

253

11.5

65.1

5.6

1.0

21.0

18.1

25

10

130

KHA036

510CF

208/230-3

187

253

11.5

65.1

5.6

1.0

21.0

18.1

25

10

130

KLA142

310BE

208/230-1

197

253

23.9

95.4

4.1

0.8

34.8

28.8

50

8

113

KLA142

510CE

208/230-3

187

253

15.3

82.0

5.6

1.0

25.8

21.9

35

10

108

KHA042

310BF

208/230-1

197

253

23.9

95.4

3.9

0.8

34.6

28.6

50

8

114

KHA042

510CF

208/230-3

187

253

15.3

82.0

5.0

1.0

25.2

21.3

35

10

111

KLA148

310BE

208/230-1

197

253

23.7

116.0

4.5

1.9

36.1

30.1

50

8

108

KLA148

510CE

208/230-3

187

253

14.7

92.0

7.8

2.2

28.4

24.7

35

10

96

KLA148

610CE

460-3

414

506

7.0

46.0

3.3

1.2

13.3

11.5

20

14

180

KHA048

310BF

208/230-1

197

253

23.7

116.0

3.7

1.9

35.3

29.3

50

8

111

KHA048

510CF

208/230-3

187

253

14.7

92.0

5.8

2.2

26.4

22.7

35

10

104

KLA160

310BE

230-1

207

253

27.8

130.0

6.2

1.9

42.9

35.9

60

8

100

KHA060

310BF

230-1

207

253

27.8

130.0

6.5

1.9

43.2

36.2

60

8

99

AWG—

American Wire Gage

FLA

—Full Load Amps

IFM

—Indoor Fan Motor

LRA

—Locked Rotor Amps

MCA—

Maximum Circuit Ampacity

OFM

—Outdoor Fan Motor

RLA

—Rated Load Amps

*Voltage limits between which the unit will operate satisfactorily

tif other than 75 C copper wire is used, determine size from unit ampacity and the National Elec­

trical code. Voltage drop of wire must be less than 2% of unit rated voltage Maximum wire

length is for one way along the wire path from unit to service panel

:(;Maximum dual element size

SINGLE-STAGE HEAT S COOL-

MANUAL CHANGEOVER

SINGLE-STAGE HEAT S COOL-

AUTOCHANGEOVER

JUMPER-H------------------- 1

CONTACTOR

TERMINALS

(SEE UNIT WIRING LABEL)

—♦frrw^--- '

------->n-rvri —

HIGH-VOLTAGE
PIGTAIL LEAD

FIELD-SUPPLIED
DISCONNECT PER NEC

3-PHASE

UNITS ONLY

. Field Low-Voltage Wiring

.Field High-Voltage Wiring

. Factory Low-Voltage Wiring

, Factory High-Voltage Wiring

NOTE:

For

manual

changeover

applications,

use

thermostat

part

no.

HH01AD042

with

subbase part no HH93AZ042, or thermostat part no HH01AD040 with subbase part no
HH93AZ040

For automatic changeover, use thermostat part no. HH07AT174 with subbase part no.

HH93AZ096; or thermostat part no HH10AD041 with subbase part no HH93AZ041.

Fig. 8—High- and Low-Voitage Connections

Advertising
This manual is related to the following products: