Cooling section start-up and adjustments, A caution – Carrier 48KHA User Manual

Page 14

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 6—Model 48KHA,KLA Air Delivery (cfm)*

at Indicated External Static Pressure and Voltage (cont)

MODEL

48-

UNIT

VOLTS—

PHASE (60 Hz)

BLOWER

MOTOR

SPEED

COILt

EXTERNAL STATIC PRESSURE (in. wg)

208V

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

230V or 460V

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Low

Heat
Cool

1440
1435

1435
1430

1425
1420

1415
1410

1400
1395

1385
1380

1365
1355

1340
1330

1305
1290

1730
1725

1720
1710

1700
1685

1675
1660

1645
1625

1601
1585

1560
1545

1520
1495

KHA048

208/

230-3

1470
1445

Med

Heat
Cooli

1755
1745

1740
1730

1725
1710

1700
1680

1665
1645

1625
1600

1580
1550

1530
1500

1470
1440

1970
1950

1945
1920

1910
1880

1875
1840

1825
1790

1775
1735

1720
1685

1660
1625

1600
1570

High

Heat
Cool

1950
1925

1920
1890

1880
1850

1940
1810

1795
1765

1750
1715

1700
1665

1645
1615

1590
1560

2175
2130

2130
2085

2085
2035

2030
1980

1970
1920

1905
1855

1840
1790

1765
1720

1695
1650

KLA160

230-1

Low

Heatt
Cool

1610
1595

1600
1585

1580
1575

1560
1550

1530
1515

1495
1475

High

Heat
Coolj:

2375
2270

2280
2185

2185
2100

2095
2015

2000
1930

1905
1840

Low

Heat
Cool

1880
1875

1875
1865

1860
1840

1825
1790

1770
1725

1700
1650

KHA060

230-1

Med

Heat^:
Cool

2130
2075

2075
2025

2015

1965

1955
1900

1890
1835

1810
1760

High

Heat
Coolj:

2345
2255

2260
2175

2180
2100

2095
2020

2010
1945

1930
1865

*Air delivery values are without air filter. Deduct field-supplied air filter

pressure drop to obtain external static pressure available for ducting

tHeating airflow values are with a dry coil Cooling airflow values are with

a wet coil.

frThese airflow values are at the factory heating and cooling motor speed

setting.

A dash (—) indicates portions of the table that are beyond the blower
motor capability or that are not applicable

NOTE: Do not operate the unit at a cooling airflow that is less than 350

fpm per each 12,000 Btuh of rated cooling capacity Indoor coil frosting
may occur at airflows below this point.

NOTE:

The igniter continues to spark for approximately 10

seconds after burners are ignited.

LIMIT

AND

PRESSURE

SWITCHES-Furnace

limit

switch (see Fig. 10) closes gas valve if leaving-air tempera­
ture exceeds 175 F.

Normally closed limits switch completes control circuit
through pigtail lead W to gas valve 5F. See Fig. 10. Should
leaving-air temperature rise to 175 F, switch opens and W
control circuit breaks. Any interruption in W control circuit
instantly closes gas valve and stops gas flow to burners and
pilot. Blower motor continues to run until time-delay
sequence of heat relay is completed.

When air temperature at limit switch drops to the low-tem­
perature setting of limit switch, switch closes and com­
pletes W control circuit. Electric-spark ignition system

cycles emd unit returns to normeil heating operation.

BLOWER SAFETY SWITCH-BIower safety switch is a
temperature-actuated switch connected in parallel with con­
tacts of heat relay. Function of switch is to activate blower

should gas valve fail to close when thermostat is satisfied.
Safety switch is mounted on blower divider panel. When
temperature at safety switch reaches approximately 175 F,
switch closes to start blower. Switch opens when tempera­
ture at switch drops to approximately 116 F.

Cooling Section Start-Up and Adjustments

A CAUTION

Complete required procedures given in Unit Prepara­
tion section before starting unit.

Do not jumper any safety devices when operating unit.

Do not operate compressor when outdoor temperature
is below 55 F (single-phase units) or 40 F (3-phase

units).

Do not permit compressor to rapid cycle. Allow 5 min­
utes between cycles to prevent compressor damage.

CHECKING COOLING CONTROL OPERATION-Start
and check unit for proper cooling control operation as
follows:

1. Place room thermostat selector switch in OFF position.

Observe that blower motor starts when fan switch is
placed in ON position and shuts off when fan switch is
placed in AUTO, position.

2. Place selector switch in COOL position and fan switch

in AUTO, position. Set cooling control below room tem­
perature. Observe that compressor, condenser fan and

evaporator blower motors start. Observe that cooling
cycle shuts down when control setting is satisfied.

3. When using an automatic changeover room thermo­

stat, place both selector and fan switches in AUTO,

positions. Observe that unit operates in heating mode
when temperature control is set to call for heating
(above room temperature) and operates in cooling mode
when temperature control is set to call for cooling
(below room temperature).

CHECKING

AND

ADJUSTING

REFRIGERANT

CHARGE—Refrigerant system is fully charged with R-22
refrigerant, tested and factory sealed. For most applica­
tions, factory charge is the correct amount for best perform­
ance; however, this charge may require a slight adjustment

to attain rated performance.

NOTE:

Adjustment of refrigerant charge is not required

unless unit is suspected of not having proper R-22 charge.
For all applications, correct R-22 charge for best perform­
ance is charge that results in a suction gas superheat of 5 F

at compressor inlet when unit is operating at ARI rating
conditions of 95 F db outdoor and 80 F db/67F wb indoor.

A superheat charging label is attached to outside of com­
pressor access door. Label includes a Field Superheat

Charging Table and a Required Suction-Tube (F) tempera­
ture chart.

Table 7 is intended for use when minor unit charge adjust­
ments are required. For large adjustments, evacuate unit

and weigh in cheirge according to unit rating plate. Use
Table 7 to approximate charge if ARI rating conditions can-

14

Advertising
This manual is related to the following products: