Carrier 17CB User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

MOTOR CURRENT CALIBRATION (Electronic
Capacity Control/Motor Drive)

1. Establish a steady motor current value for this

calibration.

Open

guide

vanes

manually

(capacity control to “Inc”) until full load
current is reached. Motor current calibration
(Fig. 8) may need to be turned counter­
clockwise to permit vanes to open further.
Do

not

exceed

105%

of

nameplate

full

load

amperes.

If system load is sufficient to maintain full

load current for a period of time, caUbrate at
this condition. With small loads, pull down to
and maintain design leaving chilled water
temperature (capacity control at “Hold”) and
calibrate at this condition.

Setting Operating Controls — Electronic

Fig. 8 — Capacity Control Module

(Electric Motor Drive)

2. Measure motor current at selected condition.

Determine its percentage of full load motor
current.

3. Use this percentage figure to set the electrical

demand adjustment (Fig. 8) per the following
table:

Percent of Full

Load Motor Current

105

85 or above
65 to 84
45 to 64
below 45

Electrical Demand

Adjustment Setting

100 percent

80 percent

60 percent

40 percent

Control cannot be
calibrated

4. Turn the motor current calibration adjustment

fully clockwise. The guide vanes will close part
way.

5. Turn the thermostat adjustment (Fig. 8) to

COOLER (fully counterclockwise).

6. Set capacity control at “Inc” position.

7. Slowly turn the motor current calibration

counterclockwise. Allow the guide vanes to
open until motor current reaches 5% above the
electrical demand setting.

NOTE; There is a time lag of several seconds

due to feedback capacitance in the motor
current circuit. When the motor current cali­
bration setting is adjusted, allow for this time

lag.

8. Check the foregoing motor current calibrations

with

machine

under

“Auto”

control

as

follows:

a.

Close vanes manually (capacity control to

DEC).

b.

Turn capacity control to AUTO. Vanes

should stop opening at electrical demand
setting.

9. If control was calibrated at less than 100%

load, turn electrical demand adjustment setting
to 100%. Control is now automatically cali­
brated for 100% full load current.

10. If control cannot be calibrated with above

procedure, check voltage signal from signal
resistor in starter. At 100% full load current,
voltage between terminals 23 and 24 inside
control center must be 0.5 ± 0.1 volts. If not
in this range, check sizing of resistor in starter.

Both

excess

motor

current

and

chilled

water temperatures below the thermostat set point
(Fig. 8) will override the capacity control setting.
If the capacity control knob is in the “Inc”
position, the guide vanes will stop opening. With

the knob in any of the other positions, the vanes

will close as needed.

The motor current limiting circuit operates in

two steps.

At 100% full load motor current, the vanes

will stop opening further. If the motor current
should increase to 105% due to some change in

load conditions, the vanes will close until the
motor current is reduced to about 102%.

If the motor current is reduced to 98% or

below, control again operates in response to chilled
water temperature.

The electrical demand adjustment permits the

operator to set the maximum current drawn by the
motor and thus minimize the electrical demand
rate during off-season operation.

CHILLED WATER CALIBRATION (Electronic
Controls)

1. Turn throttle range adjustment (Fig. 8 and 9)

fully clockwise.

A

i.

12

Advertising