*A clearance of 31^" is the absolute minimum, A clearance of 10” is

recommended.

NOTE: Remove unit front cover for controi box access.

Fig. 2 — Minimum Required Fan Coil Unit

Clearances

4, Select walls that are;

a. Strong enough to support the weight of the unit (see

Tables 4A-4D for unit operating weight).

b. Accessible to convenient condensate drainage.
c. Free of obstacles that may block air circulation to the

fan coil.

d. Outside walls (if possible) to make piping easier,

5. Place top of fan coil unit as high on wall as possible, mak­

ing sure that unit is at least 3 ’/i in. down from ceiling to
permit proper airflow (the recommended clearance is

10 inches). Also, make sure that the unit is not placed

directly over anything that would prevent filter removal
or block airflow.

6, Make sure units are easily accessible to electric power.
7. Reirigerant piping can enter the unit through the

prepunched

holes. Refrigerant piping can run down along the wall, to
the right or left along the wall, straight through the wall,
or into the wall (recommended location: right rear).
See Fig, 5, Once the piping is through the wall, it can run
inside walls, in ceilings, between floors, or straight to
the outside. See Fig. 6 for maximum line lengths. See
Table 5 for System Piston Guide and Refrigerant
Charging.
NOTE: Run refrigerant piping as directly as possible, and

avoid any unnecessary turns or bends.

8. Condensate piping can be directed through the inside wall

to an approved drain or directed straight outside,

NOTE: The piping hole for condensate line must be made
at a downward slope to ensure proper drainage. See Mount

Mounting Bracket on Wall section below for details.

Step 3 — Mount Mounting Bracket on Wall

1. Decide how refrigerant will be piped. If necessary, knock

out the appropriate pre-punched holes (Fig. 5) on unit for

piping and electrical connections.

2. Remove bracket from fan coil unit by pulling it down

from fan coil unit bottom as shown in Fig, 7.

3. Using a carpenter’s level, fasten mounting brackets

into

the studs in the wall

at least 10 in. away from the ceiling

with all the screws provided. Always be sure to insert screws
into the top 2 holes indicated in Fig, 7. Make sure the
attached bracket will support a 200

Tb

vertical load. For

a masonry wall, anchor shields can be used to attach bracket
to the wall.

4. Temporarily hang unit on bracket to check location and

level.

A CAUTION

If mounting bracket is not mounted level, the indoor sec­
tion will be mounted unevenly, and condensate drain­
age water may drip onto the floor. Also, a gap between

the bracket and the wall may result in vibration and noise
from the indoor section.

5. Mark and cut condensate and piping holes.

a. For piping through the wall, mark the wall below the

condensate connection and cut a 2'/i-in. hole into the
wall at either point “A” or point “B” in Fig. 8.

NOTE: The 2’/2-in hole must be made at a downward

slope to ensure proper condensate drainage. See

Fig. 9. Slope condensate line at a minimum pitch of

'A

in, per foot of line. The condensate line cannot be

run up for upper piping connections — only refriger­

ant lines may be run up.

b. Push the wall sleeve (factory supplied with the xmit)

through the 2‘/

2

-in. wall opening.

Table 3 — High Wall Unit Package Contents

ITEM

QUANTITY

Unit Mounting Template

1

Unit Mounting Bracket

1

1-in. Lag Screws for Unit Mounting

8

Hollow Wall Anchor Bolts for Unit Mounting

5

Wall Sleeve with Wall Cap

1

Infrared Wireless Remote Control

1

AAA Batteries (for Remote Control)

2

Remote Control Mounting Bracket

1

ya-in. Lag Screws for Remote Mounting Bracket

2

35 ft High Voltage Power Wiring

40QNB009 (3-Wire with Ground)

1

40QNEQ09 (2-Wire with Ground)

1

40QNB012 (2-Wire with Ground)

1

40QNH012 (2-Wire with Ground)

1

35 ft High Voltage Control Power Wiring (3-Wire)

1

35 ft Low Voltage Thermistor Wiring

1

Owner’s Manual

1

Installation Instructions

1

Warranty Registration Card

1