Installation – Desa VSL18NT User Manual

Page 13

Advertising
background image

www.desatech.com

116292-01D

13

WARNING: Never use an open

flame to check for a leak. Apply a

noncorrosive leak detection fluid

to all joints. Bubbles forming show

a leak. Correct all leaks at once.

CAUTION: For propane/LP

gas, make sure external regula-

tor has been installed between

propane/LP supply and heater.

See guidelines under

Connect-

ing to Gas Supply, page 11.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

heater regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply a noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Reconnect heater and equipment shutoff

valve to gas supply. Check reconnected fit-

tings for leaks.

Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 17).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter for natural gas

(see Figure 18) or propane/LP supply tank for

propane/LP gas, to equipment shutoff valve

(see Figure 19). Apply a noncorrosive leak

detection fluid to all joints. Bubbles forming

show a leak.

4. Correct all leaks at once.

Figure 19 - Checking Gas Joints for

Propane/LP Gas

Propane/LP
Supply Tank

Figure 18 - Checking Gas Joints for

Natural Gas

Equipment
Shutoff Valve

Gas
Meter

INSTALLATION

Continued

PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 17).

2. For natural gas open main gas valve located

on or near gas meter. For propane/LP gas open

propane/LP supply tank valve.

3. Make sure control knob of heater is in the OFF

position.

4. Check all joints from equipment shutoff valve

to thermostat gas valve (see Figure 18 or 19).

Apply a noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Light heater (see Operating Heater, page 14).

Check all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to Appli-

ance

, page 15).

8. Connect ignitor wire and replace front panel.

Figure 17 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff Valve

Equipment
Shutoff Valve