AIR FOR

COMBUSTION

AND

VENTILATION

Continued

Figure 2 - Ventilation Air from Inside Building

Or

Remove

Door into
Adjoining

Room,

Option 3

Ventilation Grills

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room,

Option 1

Continued

WARNING ICON

G 001

WARNING

If the area in which the heater may be operated is smaller than
that defined as an unconfined space, provide adequate combus-
tion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilat-
ing to an adjoining unconfined space, you must provide two permanent
openings: one within 12" of the ceiling and one within 12" of the floor on the
wall connecting the two spaces (see options 1 and 2, Figure 2). You can also
remove door into adjoining room (see option 3, Figure 2). Follow the National
Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and
Ventilation
for required size of ventilation grills or ducts.

WARNING ICON

G 001

WARNING

Rework worksheet, adding the space of the adjoining unconfined
space. The combined spaces must have enough fresh air to supply all
appliances in both spaces.