Hydraulically driven centrifugal pumps – Delavan M125 User Manual

Page 5

Advertising
background image

Toll Free: 1-866-DELAVAN (335-2826) • PH: 612-333-3189 • Toll Free Fax: 1-888-726-5906 • Fax: 612-333-3231

Document HD Magnum Install 3.15.06

Hydraulically Driven Centrifugal Pumps

5

Typical Flow Control

for Closed Center

(LS) Systems

Closed and Load Sensing Operation

1. With the pump installed on the sprayer (as shown in the

Plumbing Recommendations illustration on the facing
page), fill the pump with liquid by opening the inlet ball
valve.

2. Connect the hydraulic hoses to the remote outlet on the

tractor. Use the motor remote outlet if your tractor has
one.

3. Adjust the flow control on the tractor remote outlet to the

lowest flow position. Failure to start in the lowest flow
position could damage the pump and void the warranty.

4. Open the agitation line all the way open and and open

the boom control valves. Start the tractor and increase
the engine speed to the desired speed used when
spraying. Engage the hydraulic remote to start the
pump. At this time, make sure the pump is primed.

5. Adjust the sprayer pressure. Turn off the agitation line

and with the boom control valves open, adjust the flow
control to get the desired spraying pressure. Do not
exceed the sprayer pump pressure rating.

6. Open the agitation line until the desired agitation is

achieved.

7. Readjust the spray pressure by adjusting the hydraulic

flow control on the tractor.

Open Center Operation

1. With the pump installed on the sprayer (as shown in the

Plumbing Recommendations illustration on the facing
page), fill the pump with liquid by opening the inlet ball
valve.

2. Connect the hydraulic hoses to the remote outlet on the

tractor.

3. If the pump is model M200-39070-2 being used with a

large open center system with a flow rate over 15 GPM,
then open the bypass screw on the on the side of the
motor two turns.

4. Open the agitation line all the way, and open the boom

control valves. This will assist the pump in priming.

5. Start the tractor and let the engine run at idle.
6. Increase the engine speed to the desired speed for

spraying.

7. Close the agitation line until the desired agitation is

achieved.

8. Adjust the spray pressure with the boom control valve.
9. If using the bypass screw on the motor, close the bypass

as much as possible without exceeding the desired
maximum spraying pressure or the rating of the pump.

On some open center systems, operation of the sprayer
pump will lower the system pressure to a point where the
attempted operation of additional hydraulic implements
at the same time results in poor operation of both. In this
case, one of the functions will have to be turned off to make
the other one work correctly.

Advertising