NOTE: MINIMUM CLEARANCE FOR

SINGLE WALL STOVEPIPE IS 18 INCHES.

FOR DVL PIPE, THE MINIMUM IS 8

INCHES.

EXTEND-A-CAP ASSEMBLY

MINIMUM

CLEARANCE:

(NOTE BELOW)

COMBUSTIBLE WALL

THIMBLE ASSEMBLY

PIPE (AS REQUIRED)

RIGID PIPE

SPACER

RIGID TEE

ACCESS DOOR

(FOR CLEANING)

1 INCH AIR GAP

10

Adjustable Sleeve until the base of the Wall

Pass Through is flush against the masonry

(Fig.17) NOTE: The Wall Pass Through

must protrude a minimum of 2" into the

room (Fig.16).

Attach the 10" Long Rigid Pipe Section to the

front of the Wall Pass Through with four sheet

screws through the L-brackets (Fig.15, Fig.16)

Position the appliance, at it’s final location.

STEP FOUR: Push the Adjustable Sleeve from

the Wall Pass Through into the branch of the

tee. Connect Adjustable Sleeve to Tee Branch

with the pre-formed buttons. Recommended

to grout in place with a high temperature grout

(Fig.15, Fig.16).

STEP FIVE: Slide the Wall Pass-Through

through the square trim plate and into the

Figure 15