5

APPLICATION AND LISTING

DuraLiner is a double-wall, insulated all-

fuel reliner for masonry chimneys, used for

natural draft venting of gas, liquid and solid

fuel appliances. DuraLiner is listed to UL

1777 and ULC S635 under listing file number

MH14420, where maximum continuous

flue gas outlet temperatures do not exceed

1000°F/538°C (UL 1777) or 1200°F/650°C

(ULC S635). DuraLiner is approved for

installation with zero clearance between

the liner and masonry, plus zero clearance

between the masonry and combustibles.

When the Transition Anchor Plate is used,

Round DuraLiner pipe can be coupled to a

Duravent factory built 103HT chimney system

at the end of a masonry enclosure.

GENERAL INSTALLATION

INSTRUCTIONS

Follow both these and the appliance manufac-

turer’s instructions and manual for maximum

efficiency and safety. Connect only one flue

liner per appliance. DO NOT mix or match

with other products or improvise solutions-

(You may void warranties). DO NOT modify

parts.

Contact your local building official or fire

department regarding permits, restrictions,

and installation inspection in your area. Have

a professional installer thoroughly inspect (to

code requirements) and clean the existing

masonry flue of tar glaze creosote before

relining. The chimney should be checked

for cracked, loose or missing bricks, mortar,

or other materials that could inhibit correct

installation of the liner system. Make

necessary repairs prior to starting install.

Do not place insulation or other materials

other than specified in these instructions

around the liner or in required air spaces.

Determine if your setup is an open hearth

(Fig.1) or wall breach installation (Fig.2). Also

determine the available size of your chimney

and the corresponding allowable DuraLiner

size. (Fig.3)

• If you have an open hearth setup, verify

your flue size, and the fireplace opening

and depth before you purchase your

appliance and reliner.

• If you have a wall breach tee installation

setup, verify your flue size and chimney

height from tee, before you purchase your

appliance and reliner.

DuraLiner shall be sized not less than that

specified in the appliance manufacturer’s

instructions. Vent sizing is especially important

in areas with low ambient temps and low

temp flue products. Determine the required

size of DuraLiner and the correct Appliance

Connector (follow appliance manufacturer’s

recommendations). There are three different

types of appliances connections (Fig.4).

Figure 4

ROUND CONNECTOR

HIGH TEMPERATURE

SEALANT
APPLIANCE

APPLIANCE INSERT

HIGH TEMPERATURE

SEALANT

ROUND CONNECTOR

OVAL CONNECTOR

HIGH TEMPERATURE

SEALANT

APPLIANCE