TEE-SUPPORTED INSTALLATIONS

Tee-Supported installations are used when

passing through a wall to an outside chimney.

The required parts and general configuration

are as shown in Figures 23, and 24.

1. Place Appliance: Position the appliance

according to the manufacturer’s instructions.

2. Cut and Frame Opening: Cut

14-1/4 inch diameter holes in the inner and

outer walls. The center of these holes should

be aligned with the center of the stove’s flue

outlet collar. For new construction, prior to

sheetrock or other covering of the wall studs is

applied, frame a square opening between the

studs, as specified in Table 2. ( Figure 25).

Should it be necessary to go through concrete,

masonry, or cinder-block, a 14-1/4 inch

Figure 25

14 1/2”

14 1/2”

Figure 24

PIPE SECTION

6-INCH OR 9-INCH

SDP-P

WALL THIMBLE

SDP-WT

PIPE

SDP-P

TEE

SDP-T

TEE SUPPORT

SDP-TS

TEE CAP

(COMPONENT OF

SDP-T)

TEE CAP

COMPONENT OF

SDP-T

REMOVABLE

TRAY

(COMPONENT

OF SDP-TS)

5/16 x 3” LAG

SCREWS

(6 REq) NOT

FURNISHED

Figure 23

WARNING:

VENTILATED

FLASHING MUST

BE USED WITH

ENCLOSURES.

ALLOW 1/2 INCH AIR

SPACE BETWEEN BASE

OF FLASHING OR COVER

AND ENCLOSURE

FRAMING.

TYPICAL

THRU-THE-WALL

TEE- SUPPORTED

INSTALLATION

ACCESS DOOR

FOR CLEANING

FRAMED

ExTERIOR

ENCLOSURE